Test Procedure
© b2 electronic GmbH
DHV0086 Rev06
60
Step
Procedure
(Configure auto test sequence)
NS15: Arc Management Mode
only applicable for VLF withstand testing
Select one of the following arc
management modes:
• Trip out on Arc
• Burn on Arc
Fix the dwell time:
• Min. dwell time: 1 min
• Max. dwell time: 5 min
NS16: Overload during test
Set action to be taken in case of overload:
• No Action (default)
• Fail: Runs to end
• Fail. Immed. Stop
NS17: Voltage not reached
Set action to be taken in case voltage is
not reached:
• No Action (default)
• Fail: Runs to end
• Fail. Immed. Stop