Programming
DUO DMX
Gateway
30 b.a.b-technologie gmbh
DUO DMX
Gateway
5.3.2.1
LINKING OF KNX GROUP ADDRESSES
The DMX channels of the two outputs and the created scenes must be
linked to group addresses if you want to control devices with
"
Extension
"(Art.-Nr. 12000), "
KNXnet / IP
"(Art.-Nr. 12010), "
KNX / TP
"
(Art.-Nr. 12020) and „
Extension SR
“ (Art.-Nr. 12100), „
KNXnet/IP SR
“
(Art.-Nr. 12110), „
KNX/TP SR
“ (Art.-Nr. 12120). First of all, addresses
must be available in the group address management for this purpose.
There are two possible ways of achieving this: 1. Set up group addresses
in the
DMX configurator
, or 2. use ESF data import.
Figure 34: Group address management
SET GROUP ADDRESSES WITHIN THE DMX-CONFIGURATOR
If no appropriate ESF file with the corresponding group address exists, the group addresses can be
created directly in the DMX-Configurator. Proceed as follows:
1.
Create a Main-, Middlegroup:
Click the right mouse button into the empty group address field while "
group addresses
" is
checked. You will be prompted to create a new main group and can assign a name. Then click
on the main group with the right mouse button and create a new Middle group.
2.
Setting up a group address
The required group address is set up by right-clicking on the middle group. A window then
appears, in which “Number“, “Name“ and “Object type“ can be specified.
Figure 35: set group addresses