WWW.BALTIMOREAIRCOIL.COM
10
Rigging
Guide
Plenum
Side
Coil
Connections
Figure 15.
Coil Module End
Figure 14b.
Detail of Corner Column
Corner Column
78” or 97”
Length
of “D” Seal
42” Length
of “D” Seal
5/8” Space
Between the
Rigging Guide
and “D” Seal
Rigging Guide
5/8”Space
Between the
Rigging Guide
and “D” Seal
Rigging Guide
(4 places)
Figure 14a.
Coil Module as Seen from the Plenum Side
14b
“D” Seal
“D” Seal
7. Before rigging the coil modules, wipe any moisture and debris from the corner columns
and apply “D” seals (BAC part # 271665) at two locations on each coil module as
shown in
Figure 14b.
± 1/2°
X
+1°
-0°
OK
Figure 16.
Coil Module Level Tolerance as Seen from the
Plenum Side
Figure 17.
Coil Module Level Tolerance as Seen
From the Coil Module End
8. Lift the coil module and verify that it is level. Adjust lifting devices as
necessary to level the coil module before attempting to set. The coil
connection of the coil module weighs more and will affect the balance.
Tolerances are given in
Figures 16 and 17.
NOTE:
Failure to level the
coil module for rigging will prevent
proper engagement of rigging
guides.
9. To engage the rigging guides,
the coil module must be
positioned between 2 3/4”
and 3 3/4” above the lower
section as it is moved towards
the plenum module. Once the
coil module rigging guides have
engaged the plenum module
corner columns, lower the coil
into final position as shown in
Figure 18.
10. Bolt the coil module to the lower
section along the louver face
flange. See
Figure 5 on page 5
for typical bolting details.
Figure 18.
Coil Module Rigging
First In
Then Down
Rigging
Guides
2 3/4” to 3 3/4”