Inspect and clean as necessary:
Start-Up
Monthly
Quarterly
Annually
Shutdown
Inspect general condition of the unit
[2]
and check unit for
unusual noise or vibration
Inspect cold water basin
Flush water distribution system/Inspect spray nozzles
Drain basin and piping
Inspect combined inlet shields and SunScreens (Single Air
Intake Units)/Inspect air intake louvers (Dual Air Intake Units)
Check and adjust water level in basins
Check operation of make-up valve
Check and adjust bleed rate
Inspect unit finish
Mechanical equipment system:
Start-Up
Monthly
Quarterly
Annually
Shutdown
Check belt condition
Adjust belt tension
[3]
Lubricate fan shaft bearings
Lubricate motor base adjusting screw
Check and lubricate optional gear drive
See gear drive section for detailed instructions and schedule
Check drive alignment
Check motor voltage and current
Clean fan motor exterior
Check fan motor for proper rotation
Check general condition of the fan
Check and unplug fan drain holes (hollow blade fans)
Check fan for uniform pitch
Check fan for rotation without obstruction
Check and recoat steel shafts with RUST VETO
®
Check basin heater and stand alone BAC heater control panel
Test vibration cutout switch
DANGER:
Rotating equipment will cause severe
personal injury or death to persons who come
in contact. Do not perform any service on or
near the fans, motors, and drives, or inside the
unit without first ensuring that the fans and
pump motors are disconnected, locked out, and
tagged out.
NOTES:
1.
Recommended service intervals are the minimum for typical installations.
Different environmental conditions may dictate more frequent servicing.
2.
When operating in ambient temperatures below freezing, the unit should be
inspected more frequently. Refer to “Cold Weather Operation” on
for
more details.
3.
Tension on new belts must be readjusted after the first 24 hours of operation
and quarterly, thereafter.
Recommended
Maintenance
Intervals
[1]