CAUTION
Do not cover units with PVC eliminators or fill with a plastic tarpaulin. Temperature increase due
to sun radiation could deform the fill or eliminators.
AUTHORIZED PERSONNEL
The operation, maintenance and repair of this equipment should be undertaken only by personnel authorized and
qualified to do so. All such personnel should be thoroughly familiar with the equipment, the associated systems
and controls and the procedures set forth in this and other relevant manuals. Proper care, personal protective
equipment, procedures and tools must be used in handling, lifting, installing, operating, maintaining and repairing
this equipment to prevent personal injury and/or property damage. Personnel must use personal protective
equipment where necessary (gloves, ear plugs, etc...)
MECHANICAL SAFETY
Mechanical safety of the equipment is in accordance with the requirements of the EU machinery directive.
Depending upon site conditions it also may be necessary to install items such as bottom screens, ladders, safety
cages, stairways, access platforms, handrails and toe boards for the safety and convenience of the authorized
service and maintenance personnel.
At no time this equipment should be operated without all fan screens, access panels and access doors in place.
When the equipment is operated with a variable fan speed control device, steps must be taken to avoid operating
at or near to the fan's «critical speed».
For more information consult your local BAC Balticare representative.
ELECTRICAL SAFETY
All electrical components associated with this equipment should be installed with a lockable disconnect switch
located within sight of the equipment.
In the event of multiple components, these can be installed after a single disconnect switch but multiple switches
or a combination thereof are also allowed.
No service work should be performed on or near electrical components unless adequate safety measures are
taken. These include, but are not limited to the following:
•
Isolate the component electrically
•
Lock the isolation switch in order to prevent unintentional restart
•
Measure that no electrical voltage is present anymore
•
If parts of the installation remain energized, make sure to properly demarcate these in order to avoid confusion
Fan motor terminals and connections may have residual voltage after unit shut-down. Wait five minutes after
disconnecting the voltage at all poles before opening the fan motor terminal box.
LOCATION
All cooling equipment should be located as far away as possible from occupied areas, open windows or air intakes
to buildings.
LOCAL REGULATIONS
Installation and operation of cooling equipment may be subject to local regulations, such as establishment of risk
analysis. Ensure regulatory requirements are consistently met.
W W W . B A L T I M O R E A I R C O I L . E U
7
2 General Information
2 General Information