c. If you are placing pickups in a freezer, mount them well away from the door to prevent sensor

freeze up from high humidity near the freezer door. An alternative location is just outside the door
which would pick up refrigerant when the door is opened.

NOTE:  Use the worksheet supplied with the monitor to document location and lengths of tubing for later 
zone setup information.   
Protect tubing in high traffic areas using conduit and junction boxes.  In wet or potential wash down 
locations you should use the wet location filter kit p/n 3015-5748. (See end of line Best Practices Below). 

Figure 2.  Best Practices:  End of 

Line Filter for Dry Locations

 

Figure 3.  Best Practices:  End of Line Filter for Wet Locations 

(Splash Guard Accessory Part Number 3015-5748) 

8. CONNECT TUBING:  Connect tubing to the monitor using best practices for cutting and coupling air sample

tubing (see figures 4 and 5).  PTC (push-to-connect) connectors are highly recommended for tubing
connections.  In addition, ensure that all tubing cuts are “squared” (perpendicular to the tubing) to avoid
sharp angles that could damage O-rings.

Figure 4.  Tubing Connections (Best through Worst)

 

Figure 5.  Best Practices: Tubing Cuts 

9. MOUNT THE PURGE FILTER:  Mount the charcoal purge filter using the supplied bracket.  Be sure to mount

the filter near the monitor so that it is accessible when filter replacement is required.

10. CONNECT FILTER’S “FLOW OUT” SIDE:  Use appropriate tubing to connect the “OUT” side of the charcoal

filter to the “PURGE port” on the monitor.

Summary of Contents for HGM-MZ

Page 1: ...all internal wiring terminations and connections 6 RUN SAMPLE TUBING Locate the positions of remote air sample points and run air sample tubing back to the monitor making note of the length of the tu...

Page 2: ...ces End of Line Filter for Dry Locations Figure 3 Best Practices End of Line Filter for Wet Locations Splash Guard Accessory Part Number 3015 5748 8 CONNECT TUBING Connect tubing to the monitor using...

Page 3: ...the monitor must be put in service mode when refrigerant is released e g during maintenance to prevent premature purge filter contamination See Figure 7 Figure 6 Outdoor Filter Mounting Example Optim...

Page 4: ...HGM MZ Refrigerant Monitor Quick Start Installation Instructions Revision 2 4 P N 3015 9003 Figure 8 Chiller Installation Example Figure 9 Typical Refrigeration Rack Installation...

Page 5: ...nes refrigerant type alarm limits and sample lengths for each zone If splitters are used on one or more zones a Be sure to keep tubing lengths the same beyond the splitter b DISTANCE total for a parti...

Page 6: ...HGM MZ Refrigerant Monitor Quick Start Installation Instructions Revision 2 6 P N 3015 9003 Figure 11 Configuring the Number of Installed Zones Figure 12 Accessing the Zone Setup Screen...

Page 7: ...ion 2 7 P N 3015 9003 Best Practice Tip Press the right arrow button twice to move to the next zone Figure 13 Zone Setup Directions Figure 14 Splitter Example Illustrating Proper Tubing Length Practic...

Page 8: ...Either put the target zone on hold for continuous operation or wait until the monitor is polling that specific zone e Have someone view the information at the monitor for the zone to be tested and at...

Reviews: