HGM-MZ to N2 Communications Adapter 

Rev 1 (P/N 3015-5514) 

 

 

HGM 

Addr 

A5 

A6 

A7 

A8 

Switch Positions 

 

HGM 

Addr 

A5 

A6 

A7 

A8 

Switch Positions 

Off 

Off 

Off 

Off 

 

 

On 

Off  Off  Off 

 

Off 

Off 

Off 

On 

 

 

On 

Off  Off 

On 

 

Off 

Off 

On 

Off 

 

 

10 

On 

Off 

On 

Off 

 

Off 

Off 

On 

On 

 

 

11 

On 

Off 

On 

On 

 

Off 

On 

Off 

Off 

 

 

12 

On 

On 

Off  Off 

 

Off 

On 

Off 

On 

 

 

13 

On 

On 

Off 

On 

 

Off 

On 

On 

Off 

 

 

14 

On 

On 

On 

Off 

 

Off 

On 

On 

On 

 

 

15 

On 

On 

On 

On 

 

 

Since the HGM is the only node on the adapter-to-HGM interface, address 1 is normally used.  Be sure to set 

the same address on the adapter and the HGM main board DIP switches. 

 

5.  Configuring the HGM-MZ with MZ-RD or Laptop PC 

The only HGM parameters that are changeable through Metasys are the alarm thresholds.  Configuring the 

HGM for refrigerant type and length of tubing for each zone (zero length to disable a zone) must be done with 

the MZ-RD remote display or a laptop PC.  Refer to the appropriate Bacharach instructions for configuring 

these items.  HGM’s are commonly custom-configured at the factory per the customer’s needs, so field 

configuring these parameters may not be necessary. 
If configuring the HGM-MZ with an MZ-RD, the communications adapter’s presence will not affect the 

standard configuration procedure.  If configuring with a laptop PC, temporarily disconnect the HGM-MZs 

RS-485 cable from the adapter until configuration is complete and the laptop is disconnected. 

Summary of Contents for HGM-MZ

Page 1: ...g through Metasys Leak Spill Evacuate Each alarm threshold can be set through Metasys The N2 Communications Adapter can be used in conjunction with the MZ RD Remote Display if desired Wiring details and operational limitations when using the MZ RD are discussed below CAUTION The adapter is powered from the 120 240V Universal Power Supply connection on the HGM main board 120 240V is present on the ...

Page 2: ...L approved wire Wire polarity does not matter 3 If an MZ RD remote display is NOT used with the adapter refer to Figure 1 for wiring details In this case all wiring between the HGM MZ and the only external cable is the N2 communications cable 4 If an MZ RD remote display IS to be used with the adapter refer to Figure 2 for wiring details Note that when the MZ RD is used TWO RS 485 cables must be r...

Page 3: ... the BAS BUS N terminal block screw Connect the N2 wire to the BAS BUS N terminal block screw Connect the N2 REF wire to the BAS BUS REF terminal block screw Shield connection practices vary Refer to Johnson Controls Metasys N2 documents for Johnson recommended practices Options are to hard terminate the shield to the case soft terminate through a small value capacitor the shield to the case or le...

Page 4: ...ee Figure 3 for the location of adapter DIP switches A and B Switches 5 8 on the adapter s A DIP switch are used to match the node address set on the HGM s address DIP switch on the HGM main board Values from 0 15 are possible Refer to the table that follows Figure 3 HGM MZ to N2 Communications Adapter DIP Switches ...

Page 5: ...he HGM MZ with MZ RD or Laptop PC The only HGM parameters that are changeable through Metasys are the alarm thresholds Configuring the HGM for refrigerant type and length of tubing for each zone zero length to disable a zone must be done with the MZ RD remote display or a laptop PC Refer to the appropriate Bacharach instructions for configuring these items HGM s are commonly custom configured at t...

Page 6: ... 13 On On Off On 6 Off On On Off 14 On On On Off 7 Off On On On 15 On On On On 3 Take the value 0 15 from above and multiply that times 16 4 Subtract the result from the desired N2 address 5 This gives another number 0 15 Use this number and the table to set switches B5 B8 N2 Address Lower Half B5 B6 B7 B8 N2 Address Lower Half B5 B6 B7 B8 0 Off Off Off Off 8 On Off Off Off 1 Off Off Off On 9 On O...

Page 7: ...n the HGM MZ Each monitored zone in the HGM supports three levels of alarming Leak Spill Evacuate Since the Metasys N2 architecture does not support three different levels of high alarming per AI point each HGM zone is set up as THREE AI points The first AI point for a zone supports a Leak Alarm the second AI point for a zone supports a Spill Alarm and the third AI point for a zone supports an Eva...

Page 8: ...mm from Metasys N2 directed to ANY N2 slave not necessarily this one Under normal conditions you would expect to see a lot of activity on LED 4 since the N2 master is continually polling all N2 slaves on the line LED 3 will show activity based on how often the N2 master is polling the adapter versus other N2 slaves on the line If there are few N2 slaves on the line a lot of polls will be directed ...

Page 9: ...ort try swapping the communications wires on the N and N terminal block screws The HGM port uses the same labels as the HGM main board so if you match the wires to the labels polarity should not be an issue there If the adapter seems to not be functioning correctly it can be restarted without restarting the HGM simply by pressing the CPU RST button just below the A DIP switch If you restart the ad...

Page 10: ... 3015 5514 Headquarters 621 Hunt Valley Circle New Kensington PA 15068 7074 Toll Free 1 800 736 4666 Tel 1 724 334 5000 Fax 1 724 334 5001 Website www MyBacharach com E mail help MyBacharach com Printed in U S A Registered Trademark of Bacharach Inc ...

Reviews: