FULLSCALE UNITS=GPM
FULLSCALE=0
000 X 1,000
This screen allows the setting of the full scale range.
Press the UP or DOWN arrow keys to change each digit
to the desired value and the RIGHT arrow key to move
the cursor under each digit. Press the ENTER key and the
following screen will appear:
TOTALIZER MULTIPLIER
X 1,000
This screen allows the selection of the totalizer
multiplier. Press the UP or DOWN arrow keys to select
the desired multiplier and then the ENTER key. The
following multipliers are available:
X.01
X100
X.1 X1000
X1 X10,000
X10 X100,000
The following screen will appear:
CHART REVOLUTION SPEED
1 REVOLUTION IN 1 DAY
This screen allows the selection of the chart rotation
speed. The following speeds are available:
1 REVOLUTION IN 2 MINUTES
1 REVOLUTION IN 24 MINUTES
1 REVOLUTION IN 1 HOUR
1 REVOLUTION IN 1 DAY
1 REVOLUTION IN 7 DAYS
1 REVOLUTION IN 31 DAYS
- - - - - -
- - -
The two dash line positions are positions for future
chart revolution speeds.
Press the UP or DOWN arrow keys to select the desired
chart speed and press the ENTER key. The following
screen will appear:
RECORDER DAMPING
DAMPING TIME = 6 SECS.
This screen allows the selection of the amount of
damping in the response of the recorder. The damping
times available are:
NONE 6
16
40
100 240
600
These times are in seconds. Higher damping produces
smoother pen lines. Press the UP or DOWN arrow key to
select the desired value and then the ENTER key. The
following screen will appear:
-FUNCTION SELECTION-
POWER=>LINEAR
This screen allows the selection of linearization
functions for use with differential pressure transmitters,
open channel flow measurement devices or any definable
function.
Linear should be selected for the Model 2100R+.
Check the output specification of the device that is being
connected to the recorder to determine the proper power
election. The functions available are:
s
POWER=>LINEAR
POWER=>1.55
POWER=>1.58
POWER=>1.9
POWER=>1/2
POWER=>3/2
POWER=>5/2
POWER=>OPTION
The linear function is used where the transmitter output
is proportional to flow.
The 1.55 power is used with 1", 2", 3", 24" Parshall
flumes and all Lagco flumes.
The 1/58 power is used with a 6" Parshall flume.
The 1.9 power is used with Badger Meter Manhole
flumes.
The 1/2 power is used with differential pressure
transmitters where the output does not have the square
root extracted.
The 3/2 power is used with all Rectangular and
Cippoletti weirs.
The 5/2 power is used with all V-Notch weirs.
The OPTION power allows a 16 point HQ curve to be
programmed into the recorder. Consult the factory for
programming details.
Press the UP or DOWN arrow keys to select the linear
function and then the ENTER key. The following screen
will then appear:
3-4