Programming
Page 26
May 2020
DSY-PM-01378-EN-08
Test
The
Test
setting places the monitor into a special diagnostic mode that shows the current
input frequency and the accumulated input counts�
shows the layout for test
mode values� The
Test
mode makes it possible for you to see the frequency input the
monitor is measuring and is very useful in troubleshooting and noise detection�
2
1
Input
Frequency
Totalizer
Counts
Figure 11: Test mode screen
At the
Display
prompt, press
ENTER
to view the current display setting� If the current
display setting is correct, press
ENTER
to advance to the next parameter� To change the
display setting, press
UP
or
RIGHT
to scroll through the display options� Press
ENTER
to
advance to the
KFacUnit
parameter�
Select Meter’s K-Factor Unit*
At the
KFacUnt
prompt, press
ENTER
� The display shows the current K-factor unit� If the
current selection is correct, press
ENTER
to advance to the next parameter� To change
the K-factor unit, press
UP
or
RIGHT
to scroll to the correct unit, the units should match the
units that the meter was calibrated in� Press
ENTER
to advance to the
KFactor
parameter�
Enter Meter’s K-Factor*
OTE:
N
The K-factor supplied with your meter, or calculated from calibration data, is
needed to complete this step�
At the
KFactor
prompt, press
ENTER
� The most significant digit in the K-factor flashes� If
the current K-factor is correct, press
ENTER
to advance to the next parameter� To change
the K-factor, press
UP
to increment the digit until it matches the meter’s first K-factor digit�
Press
RIGHT
to advance to the next digit� Repeat this process until all K-factor digits have
been entered� Press
ENTER
to accept the K-factor and advance to the
RateInt
parameter�
OTE:
N
The number of digits available before and after the decimal point is determined
by the bore size of the flow sensor being used� The largest K-factors are associated
with the smallest bore sizes� The maximum allowable K-factor is 99999�9� The
minimum must be at least 1�000� If an out of range number is entered, the display
flashes Limit and refuses the entry�
Select Rate Interval*
At the
RateInt
prompt, press
ENTER
� The monitor flashes the current time interval� If the
current selection is correct, press
ENTER
to advance to the next parameter� To change to
an alternate time interval, press
UP
or
RIGHT
to scroll to the required time interval� Press
ENTER
to advance to the
RateUnt
parameter�