Wiring the cb-30
Page 9
April 2017
CTL-UM-01028-EN-03
Pulse Transmitter Connections
The CB-30 is designed to accept pulses from open collector transistors or dry contact closure transmitters
Before making any connections please make sure to comply with the following:
1 Always use shielded wire to protect the signal line from external noise (round shield to terminal #3)
2 Make sure the signal lines are not bundled with or touching power lines
Figure 4
shows the connection to Model PFT-3E transmitter, usually supplied with a Badger Meter Industrial Turbo meter The
Model PFT-3E provides an open collector transistor output for the CB-30
Frequency
DC to 5 kHz (high speed)
DC to 150 Hz (low speed)
Low Level
0…2V DC max
High Level
8…20V DC max
Impedance
4 7 K
W
pullup to +12V DC
VDC Current
2 5 mA steady state
Oesponse
100
m
s min pulse (high speed) 3 5 ms min pulse (low speed)
Table 4: Transmitter Count Input
MODEL PFT-3E
TRANSMITTER
RED
GREEN
BLACK
USE SHIELDED CABLE
NOTE: DO NOT GROUND
SHIELD AT METER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
25 26
21 22 23
BADGER METER
MODEL CB-30
Figure 4: Pulse Transmitter Connections