background image

METER STORAGE MODE

All E-Series Ultrasonic meters are delivered in a storage mode so that a meter alarm is not triggered  During storage mode, 

the empty pipe shows up on the LCD display as an error message, but it will not trigger a meter alarm  The meter needs to 

sense a full pipe for 24 hours for the meter to go from storage mode to normal operation  If installed when the meter is still in 

storage mode, the meter will function as expected with the addition of also displaying “err” on the flow rate screen  The meter 

will display consumption and, if connected to AMR/AMI, will send a reading to the endpoint  When the meter is in normal 

operation, the meter alarm displays immediately upon detecting the empty pipe condition  The alarm clears immediately 

after the condition is corrected and the pipe is full  Systems that support the additional alarm conditions will be notified that 

an empty pipe condition has occurred 

METER PRE-INSTALLATION

Take into account the following considerations before you begin an installation:
•  Inspect the piping around the meter for suitable conditions  The service line, valves, connections and meter must be 

watertight  Repair the piping system if pipes are corroded or damaged  

•  Install the meter in the pipeline in a horizontal or vertical position so that the flow arrow on the meter housing points in 

the same direction as water flow  Registration should be upright and protected from damage, freezing, and tampering 

•  Position the meter so it is accessible for installation, removal and reading 
•  Verify that a suitable, electrical grounding wire is properly attached to the upstream and downstream pipe connections of 

the meter  The grounding wire provides an alternative path for any electrical current that may exist across the opening in 

the line 

•  Close the curb (shutoff) valve to relieve water pressure in the line before starting the cutting operation  Provide a high-

quality upstream shutoff valve with a low pressure drop  

•  When cutting into a new section of service pipe, flush the pipe to clear chips, pipe dope or other plumbing residue 
•  For the DN15… DN32 meters, the line opening for the meter should match the laying length of the meter, allowing slight 

additional space for coupling gaskets  The inlet and outlet sides of the meter setting should be axially aligned to  

the pipe 

•  For the DN40 and DN50 meters, the line opening for the meter should match the laying length of the meter  For optimal 

performance and accuracy, it is also recommended that a minimum of five diameters of straight pipe be installed 

upstream of the meter 

•  The installed meter must not be an obstacle or a hazard to the customer or interfere with public safety 

•  DO NOT ATTEMPT TO USE ANY METER AS A LEVER OR CROWBAR TO STRAIGHTEN A MISALIGNED METER POSITION. 

THIS COULD DAMAGE THE METER. 

•  DO NOT ATTEMPT TO INSTALL A METER INTO AN OPENING THAT IS TOO LONG BY FORCING THE PIPING INTO PLACE 

WITH THE METER'S COUPLING NUTS. THIS WILL CAUSE SERIOUS DAMAGE TO THE THREADED ENDS OF THE METER  

AND HOUSING. 

•  TO AVOID POTENTIAL PROBLEMS, CORRECT ANY IRREGULARITIES IN PIPE SPACING AND MISALIGNMENT BEFORE 

PLACING THE METER INTO ITS POSITION.

E-Series® Ultrasonic Meters, Cold Water Meters

Page 6 

September 2017

ESM-UM-00255-EN-01

Summary of Contents for DN15

Page 1: ...E Series Ultrasonic Meters Cold Water Meters DN15 DN20 DN25 DN32 DN40 DN50 ESM UM 00255 EN 01 September 2017 User Manual...

Page 2: ...E Series Ultrasonic Meters Page ii September 2017 ESM UM 00255 EN 01...

Page 3: ...Meter 7 Special Fittings and Accessories 7 Installing E Series Ultrasonic Meters 7 Outdoor Installations 7 Indoor Installations 7 Installation Instructions 8 Protect Against Leakage 9 E Series Ultras...

Page 4: ...E Series Ultrasonic Meters Page iv September 2017 ESM UM 00255 EN 01...

Page 5: ...pment PRODUCT UNPACKING AND INSPECTION Upon opening the shipping container visually inspect the product and applicable accessories for any physical damage such as scratches loose or broken parts or an...

Page 6: ...al and reading Verify that a suitable electrical grounding wire is properly attached to the upstream and downstream pipe connections of the meter The grounding wire provides an alternative path for an...

Page 7: ...edded to ensure that it is not axially misaligned and that it lays evenly on the bottom of the pipe trench The backfill material covering the pipe should be placed appropriately to maintain pipe align...

Page 8: ...e nut against the meter spud end When the first threads on both the nut and the spud end coincide you will hear a slight click and feel the nut move into the starting position iii Tighten the nut by h...

Page 9: ...cape 7 Once water is flowing normally turn off the faucet E SERIES ULTRASONIC METER OPERATIONS Meter Display The Badger Meter E Series Ultrasonic meters use a nine digit Liquid Crystal Display LCD tha...

Page 10: ...feet or 100 thousand cubic meters with a resolution of 0 0001 cubic meters For DN40 and DN50 meters totalized flow displays up to 100 million gallons with a resolution of 0 1 gallons 10 million cubic...

Page 11: ...345678 10 gallons 123456 10 gallons 1234567 100 gallons 12345 100 gallons 123456 Typical Billing Units 1000 gallons 1234 Typical Billing Units 1000 gallons 12345 Cubic Feet Meter reading 1000th ft3 12...

Page 12: ...ding 7 digit reading Itron 100W 8 9 digit reading 6 digit reading 7 digit reading Itron 100W 9 digit reading 6 digit reading 7 digit reading No longer for sale 100W will transmit 9 digits through Itro...

Page 13: ...rm is sent to the endpoint NOTE No consumption data is sent to endpoint when the alarm is active Consumption data is sent to the endpoint except when Exceeding Max Flow alarm is set Reverse flow The m...

Page 14: ...o provide long term service with no maintenance The enclosure which includes the electronic meter s ultrasonic sensors battery and display is completely potted permanently sealed and non removable E S...

Page 15: ...m3 hr 4 0 gpm 1 71 m3 hr 7 5 gpm 1 71 m3 hr 7 5 gpm 1 71 m3 hr 7 5 gpm 3 2 m3 hr 14 0 gpm 4 5 m3 hr 20 gpm R Value 250 250 250 250 250 250 250 Operating Performance In the normal temperature range of...

Page 16: ...de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus...

Reviews: