Setup > Communications
For addressing information, see the
"TFX-500w Clamp-On Meter Modbus RTU Protocol"
user manual or the
"TFX-500w Clamp-On
Meter BACnet MS/TP Protocol"
user manual, available at
www.badgermeter com
An asterisk (*) indicates the parameter default
Communication
Submenus
Options/Descriptions
NETWORK TYPE
DISABLE
Either disable this feature or select a network type
*MODBUS RTU
BACNET MS/TP
SETTINGS
MODBUS RTU
ADDRESS
Numeric entry 1…127
BAUD RATE
9600, 19200, 38400, 57600, 76800, 115200
ACCESS
WRITE/READ allows full access
RESET/READ allows you to read any, but only write to Flow Total Reset (cannot
set up meter)
READ ONLY allows read only
PARITY
*NONE
ODD PARITY
EVEN PARITY
STOP BIT
*1 STOP BIT
2 STOP BITS
RESISTOR
*DISABLED
ENABLED
WORD ORDER
BIG ENDIAN
*LITTLE ENDIAN
For 32-bit numbers or data types spanning over
multiple registers, select the order of the 16-bit
word or register to match the Modbus RTU
master
TIMEOUT
*DISABLE
Numeric entry 0…10000 ms
Enter 0 ms to disable the timeout option
For networks with a predictable poll rate by the
master device, this parameter is an option to
record and display an S60 code when the meter
does not receive a message from the master
device Enter the time that the meter should
record and display a loss of communication
timeout
BACNET MS/TP
MAC ADDRESS
Numeric entry 0…254
BACNET ID
Numeric entry 0…4194303
BAUD RATE
9600, 19200, 38400, 57600, 76800, 115200
ACCESS
WRITE/READ
READ ONLY
PASSCODE
MAX MASTER
Numeric entry 1…127
PARITY
*NONE
ODD PARITY
EVEN PARITY
STOP BIT
*1 STOP BIT
2 STOP BITS
RESISTOR
DISABLED
*ENABLED
ENDPOINT
DIAL COUNT
7, *8, 9, 10
RESOLUTION
*OFF, 1, 10, 100, 1000, 10000, 0 1, 0 01, 0 001, 0 0001
PROTOCOL
*DISABLED
V1
V2
V3
When an ORION endpoint is connected to the transmitter, select the settings to
match the BEACON/AquaCUE settings Only the flow total selected for the
Home
screen will be sent
V1 protocol does not support dial counts above 7
Parameter Descriptions by Menu
Page 28
May 2021
TTM-UM-02537-EN-06