Page 36
4-11
Model M-2000 Mag Meter
Inputs/Outputs
Digital Output
Output Type
[1: Normally Open]
[2: Normally Open]
[3: Normally Open]
[4: Normally Closed]
S
The Output Type parameter lets you set the output switch to normally open or
normally closed. If normally open is selected, the output switch is open
(no current) when the output is inactive, and closed (current flows) when the
output is active.
If normally closed is selected, the output switch is closed (current flows) when
the output is inactive, and open (no current) when the output is active.
To change the Output Type, follow these steps from the
Inputs/Outputs Main
Menu
:
1. Select
Digital Output 1
,
2, 3 or 4
and press
[E]
to open the Digital Output
menu.
2. From the
Digital Output menu,
select
Output Type
,
and press
[E]
to open the Output Type display.
3. Select
Normally Open
or
Normally Closed
.
4. Press
[E]
to save the new parameter and return to the Digital Output
menu.
Hardware Type
[3: Open Collector]
[4: Open Collector]
S
The hardware type parameter lets you select the type of hardware used to drive
the output signal: either open collector or solid-state relay.
To change the Hardware Type, follow these steps from the
Inputs/Outputs
Main Menu
:
1. Select
Digital Output 3 or 4
and press
[E]
to open the Digital Output
menu.
2. From the
Digital Output menu
select
Hardware Type
, and press
[E]
to
open the Hardware Type display.
3. Select
Open Collector
or
Relay
.
4. Press
[E]
to save the new parameter and return to the Digital Output
menu.
Full Scale Frequency
[3: 1000 Hz]
S
This parameter establishes the full scale flow output frequency when the flow
rate equals the configured full scale flow.
To change the Full Scale Frequency, follow these steps from the
Inputs/Outputs
Main Menu
:
1. Select
Digital Output 3
and press
[E]
to open the Digital Output menu.
2. From the
Digital Output menu
select
Full Scale Frequency
, and press
[E]
to open the Full Scale Frequency display.
3. Set the full scale frequency value to the desired setting.
4. Press
[E]
to save the new parameter and return to the Digital Output
menu.