Programming
Page 18/47
MID_M1000_BA_02_1802
Power Line
Frequency
For an optimum operation of the meter, set Power Line Frequency
50 Hz or 60 Hz in this menu at operating location.
Excitation
Frequency
This value shows in which frequency the meter’s coils are operated.
Supported frequencies are dependent on the configured power line
frequency and meter’s size.
Note: When selecting excitation frequency, make sure to always ob-
serve that the ratio in respect of power frequency is integer.
Empty Pipe
Detection
On/Off
Fluid monitoring shows if measuring pipe has only
partly been filled with liquid. Monitoring can be
switched ON or OFF.
Note: On request, fluid monitoring can be adjusted
to fluid’s conductivity or to cable length.
Threshold
Threshold value for empty pipe detection.
For liquids with lower conductivity or long cables
the threshold value must be increased. The actual
value can be monitored in the next menu “mea-
sured”.
Measured
read only
Monitor the actual measured resistance of the
empty pipe detection function.
50 Hz
60 Hz
3.125 Hz
3.75 Hz
6.25 Hz
7.5 Hz
12.5 Hz
15 Hz