Programming
Page 26/47
MID_M1000_BA_02_1802
Pulse Width
This parameter establishes the “On” duration of the
transmitted pulse. The configurable range ist from 0
msec to 2000 ms. If 0 ms is configured, pulse width is
automatically adapted depending on pulse frequency
(pulse/pause ratio 1:1).
During the configuration the program checks if
pulses/unit and pulse width are in accordance with full
scale defined, if not an error alarm is displayed. In
case of an error alarm, scale, pulse width or full scale
need to be adapted.
Pulse/Unit
The Pulses/Unit parameter lets you set how many
pulses per unit of measure will be transmitted. The
max. output frequency of 10,000 pulses/sec. (10 kHZ)
must not be exceeded.
Frequency
This parameter establishes to define the digital output
as frequency output. Full scale frequency can be
configured from 0.01 to 10,000 Hz.
Set Min/Max
The Flow Set Point (min, max) establishes as a
percentage of full scale flow, the threshold at which the
output alarm will be activated. You can freely select
thresholds in 1% steps. Flow rates below/above the
threshold will activate the output alarm.
Preset
Amount
Preset amount lets you set the reset value for the
associated PS totalizer when the digital input is set to
Batch Reset. You can configure preset amount in the
adjusted volume unit.
Preset amount is counted down from the configured
value to 0 and a digital output shows that the preset
amount has been reached.
Out Type 1
The Output Type parameter lets you set the output
switch to “normally closed“ or “normally open“.
Out Type 2
The Output Type parameter lets you set the output
switch to “normally closed“ or “normally open“.
Flow Simulation
Flow Simulation provides analogue and digital output simulation based
on a percentage of the full scale flow in cases where no real flow is
occurring. The range of simulation includes -100% to +100% in steps
of 10% of the full scale flow. This function still remains active once you
have left the menu. It is necessary to set it to “Off” to deactivate it. If
the simulation is still active, a character “S” will be displayed in the
measuring mode.