STARTUP (SETTING BY MEANS OF LOCAL SWITCHES AND
POTENTIOMETERS)
Initial Setting
Figure 6: Initial setting
After mounting the positioner on the actuator, air and electrical input
connected, proceed as follow
Put all switches in position I This is the setting for input signal
“4 to 20 mA” and “Left mounted” (counter clockwise rotation)
Configuration Direction of Rotation of Feedback Shaft
Defined as direction of rotation of feedback shaft from the start to the end position, looking at the positioner from the front
Switch 1+2 to “R” if necessary
R= right turn (clockwise) L= left turn (counter cw)
Figure 7: Configuring direction of rotation
STARTUP (setting by means of local switches and potentiometers)
Page 9
July 2013
POS-QS-00007-EN-02