Motorized Linear Actuator
baelz 373-E45
8.4 Configuration of the DIP switches
= factory setting
The factory setting of the DIP switches is position 0, as shown.
Fig. 10: Setting the DIP switches
Switch
Function
Position 1 "ON"
Position 0
DIP 1
Set value input: voltage, V or current, mA?
current, mA
voltage, V
DIP 2
Set value input starting at 0 V / 0 mA or
2 V / 4 mA?
2-10 V / 4-20 mA
0-10 V / 0-20 mA
DIP 3
Analogue output starting at 0 V / 0mA or
2 V / 4 mA?
2-10 V and / or
4-20 mA
0-10 V and / or
0-20 mA
DIP 4
Direction of control action: valve closed with
drive spindle extended or retracted?
Drive spindle retracted
→
valve closed
Drive spindle
extended →
valve closed
DIP 5
Current position of the actuator is saved as
additional switching position "2EZ-1". See
wiring diagram, page 21.
from 0 to 1 →
save "2EZ-1"
= 2%
DIP 6
Current position of the actuator is saved as
second additional switching position "2EZ-1".
See wiring diagram, page 21.
from 0 to 1 →
save "2EZ-2"
= 98%
DIP 7, 8, 9
These 3 DIP switches define the function:
linear / split range / 11-point / inverted
s. Fig. 11, page 24
= linear
DIP 10
Defines valve characteristic using actuator
characteristic, see page 24.
Actuator characteristic
inverse equal
percentage, valve
action linear
Actuator characteristic
linear, valve action
equal percentage
DIP 11
Selects standard or Modbus mode.
Modbus mode
standard mode
DIP 12
Starts initialization run.
Set back to 0 after initialization
(s. section 8.5.2)
from 0 to 1 →
starts initialization run
N↔S
Selects normal or safety mode
position "S"
= safety mode
position "N"
= normal mode