background image

 

 

 

Page 13

 

 

Device manual 

6490B / 6490B-y / 6590B 

W. Bälz & Sohn GmbH & Co.  Koepffstraße 5  D-74076  Heilbronn  Telefon (07131) 1500-0  Telefax (07131) 1500-21

 

I.e. actual value at start of the optimisation = 60°C, target setpoint = 100°C which is a difference of 

T = 40°C. 

The needful change of the actual value can be calculated then by 

PV = 1/4 * 

T = 1/4 *40K = 10K. 

The optimisation can only be finished when the actual value is at least 60°C + 10K = 70°C. 
Cause is a process gain which does not fit (see also 3.a) and 3.b)). 

Solution: Cancel or finish the optimisation (see 5.). 

Reduce the process gain P.G in the configuration level (e.g. 1/2). 
Restart optimisation. 

 
 

5.  Cancelling the optimisation premature 

An already running optimisation shall be cancelled without recalculation of the control parameters. 
A reason for that could be e.g. a not permitted rise of the temperature over the tolerated limits during the optimisation. 
After a cancel the process gain P.G can be magnified manually to get a smoother temperature change within the next 
optimisation (see also 3.a) and 3.b)). 
 
Cancelling by: 
a)  activating manual mode 
b)  setting a setpoint once more 
c)  activating a digital input (OPEN, CLOSE, STOP, SP.2) 
d)  activating the modbus RAM-setpoint (see "Modbus documentation") 
 
Cancelling the optimisation premature, including recalculation of control parameters and process gain, can be realized by 
changing "Opt = 1" to "Opt = 0" in the configuration level during process of optimisation. 
 
 

6.  The optimisation results are not satisfying 

Reasons: 
a)  The optimisation did not run within the range the control is working after.  

I.e. the range between 60°C and 80°C was optimised, but the following control works with a setpoint change 
from 50°C to 100°C. 

Solution: At beginning of the optimisation the actual value should correspond to the first point and the initial setpoint 

to the other (target setpoint) of the desired control range (see also 2.c)). 

b)  Processes with strongly different time behaviour (e.g. fast heating up, slow cooling down) where the change of the 

actual value during the optimisation worked reverse to the following control. 
I.e. optimisation from 100°C to 50°C but the following control from 50°C to 100°C. 

Solution: If possible, optimise in the same direction the control is working after. If it has to be controlled in both 

directions, the more important direction has to be optimised. Do both directions have the same relevance, 
the slower process has to be optimised. 

c)  The actual value has not been in a stable state before starting the optimisation. 

Solution: Wait until the actual value is in a stable state before starting the optimisation. If the actual value can not get 

stabilized in the automatic mode (oscillation), an optimisation started from the manual mode is necessary. 

d)  The target setpoint could not be reached at the end of the optimisation. 

Solution: see 3) 

e)  During the optimisation the actuator must not run over the limits 

 neither 0% nor 100%. Nevertheless a completely closed 

actuator at start of the optimisation would be tolerated, i.e. in case that a de-energized plant (with closed actuator) drives 
immediately to the target setpoint at start of the optimisation. 

Solution: Set a bigger process gain and restart optimisation or just set another target setpoint. 

f)  Power supply is not stable because of too many peripherals. 

Solution: Optimisation only at times when a stable energy supply is guaranteed. 

g)  Controlling the process is almost impossible because the actuator does not fit (e.g. valve is over-sized). 

Solution: Check dimensions of the actuator, change it if necessary. 

h)  The process can not be controlled perfectly with the chosen type of controller. 

Solution: Let the optimisation run with another type of controller (PI or PID) and compare.

Summary of Contents for mCelsitron 6490B

Page 1: ...0mm Easy operation User defined operating level Digital displays for process variable and setpoint Indication of the manipulated variable at 6490B y with additional bargraph display Control structure...

Page 2: ...SP H 17 3 11 Second setpoint SP 2 at 6x90B y 1 4 4 i SP 2 17 3 12 Setpoint ramp SP r SP r 18 3 13 Ramp direction rA d 18 3 14 Delta setpoint dSP 19 3 15 Delta setpoint description 19 3 16 Process gai...

Page 3: ...ng electrical equipment certain parts of this equipment automatically carry dangerous voltages Failure to observe these instructions could therefore lead to serious injury or material damage Therefore...

Page 4: ...e Digital input OPEN Actuator opens Digital input CLOSE Actuator closes Digital input STOP Actuator persists in its current position Digital input SP 2 To switch over to the second setpoint SP 2 if co...

Page 5: ...En OPEN DI active tunE optimisation running rAMP Setpoint ramp running SP_2 Second setpoint active If one of these functions is active the SP display is alternating between the status display with the...

Page 6: ...counter with a range of 0 to 255 With each valid modbus package it counts up one unit When the counter reaches 255 it wraps around with the next modbus package and starts counting up from 0 again If...

Page 7: ...Page 7 Device manual 6490B 6490B y 6590B W B lz Sohn GmbH Co Koepffstra e 5 D 74076 Heilbronn Telefon 07131 1500 0 Telefax 07131 1500 21 2 5 Switch over to configuration level...

Page 8: ...the next configuration point is displayed Now scrolling inside the configuration level works in forward mode 2 7 Switch over to second operating level user defined operating level How to switch over...

Page 9: ...point 2a Set new value by change in individual steps and respectively 2b Set new value by continuous change with increasing speed and 3 confirm new value within 5s otherwise the previous still effect...

Page 10: ...manual mode optimisation from automatic mode Procedure of optimisation Set target setpoint SP Switch to manual mode By opening closing the actuator the actual value PV is set on a higher lower value...

Page 11: ...ion does not start no alternating tunE and manipulated variable in the setpoint display SP By switching from manual to automatic mode or by changing the setpoint in the automatic mode the optimisation...

Page 12: ...nough Solution Let the optimisation run a couple times until the target setpoint is reached exactly enough The process gain will be defined then by an iterative method what means with every run the pr...

Page 13: ...respond to the first point and the initial setpoint to the other target setpoint of the desired control range see also 2 c b Processes with strongly different time behaviour e g fast heating up slow c...

Page 14: ...of the PID three position step controller Setting range 1s to 255s 3 5 Dead band db No actuating pulses if control deviation is smaller than db Hysteresis db 2 Setting range 0 to 10th part of the scop...

Page 15: ...Alarm at a fixed limit value of PV If AL 1 2 alarm is triggered if the value set at A1 b is reached or exceeded The hysteresis defines a span between alarm state and switching back to normal state Ret...

Page 16: ...of the measuring range phys units 0 to scope of the measuring range phys units at dP 3 AL 1 3 selects Al C and Al C alarm type C see description 3 7c Lower half of the band around the setpoint negativ...

Page 17: ...value 300 C and 572 F respectively When changing dI L or dI H all values entered as physical units are rescaled expressed as percentage When a Pt100 sensor is used dI L and dI H have to correspond to...

Page 18: ...any setpoint change switching over to the second setpoint SP 2 a control function STOP CLOSE OPEN via digital input switching from manual mode to automatic mode 3 13 Ramp direction rA d Setting the d...

Page 19: ...e temperature in the tenter has to drop below the hysteresis of the alarm relay until the control of the burner is released again 1 Then the burner can be moved to its ignition position and be started...

Page 20: ...he STOP command is inactive the controller generates only an OPEN pulse according to the under temperature of 5 K instead of an OPEN pulse according to an under temperature of 15 K Example There is a...

Page 21: ...to the setpoint ramp SP r If the speed of the setpoint ramp SP r gradient is adjusted 0 75 to 0 5 times of the natural temperature rise rate temperature change in fig 1 the setpoint will be reached wi...

Page 22: ...ppressing interference signals and smoothing fast fluctuations of the actual value Formula Tf 0 04 ln input 256 Setting range 0 to 255 At FIL 0 no software filter is active The following assignment ap...

Page 23: ...s 3 24 Assigning the control function STOP to a digital input at 6x90B y 1 4 4 i St d Selection 0 No digital input is selected 1 5 Defines the number of the digital input to activate a STOP command In...

Page 24: ...controlling can be continued with a constant Y display and valve position 3 Mains power has been switched on internal manipulated variable saved manipul variable At mains failure internal manipulated...

Page 25: ...4 4 i S C Selection 0 Operation of the controller via front keyboard and modbus master is possible 1 Operation of the controller is only possible via modbus master except configuration point S C 3 33...

Page 26: ...s 6590B 5 Electrical connection The wiring diagram is located on the backplane 6490B 6490B y and on the top side 6590B of the device respectively The plug type terminals are located on the backplane o...

Page 27: ...Page 27 Device manual 6490B 6490B y 6590B W B lz Sohn GmbH Co Koepffstra e 5 D 74076 Heilbronn Telefon 07131 1500 0 Telefax 07131 1500 21 5 1 Wiring diagram...

Page 28: ...s the corresponding DI state text displayed in the SP display e g StOP CLOS Check voltage supply for digital inputs external switching contacts signal lines and electrical connection Consider the disp...

Page 29: ...f the measuring range Digital inputs high active low n c 0 V DC high 15 V to 24 V DC Displays Two 4 digit 7 segment displays LED red character height 6490B 6490B y 13mm character height 6590B 10mm Ala...

Page 30: ...via digital input DI CLOSE command via digital input DI STOP command via digital input DI Number of alarm relays RS 485 interface modbus RTU mode Standard temp range 2 4 0 C 300 C with 0 1 accuracy Al...

Page 31: ...range phys units at dP 3 Alarm 1 type C lower limit A1 C 0 to scope the of measuring range phys unit at AL 1 3 Hysteresis lower limit for A1 C HY 1 0 to 10th part of the scope of the measuring range...

Page 32: ...al Y position is not saved in case of a mains failure 1 Y bargraph is displayed actuator does not close for the time of the valve actuating time at mains recov internal Y position 0 actual Y position...

Page 33: ...Remarks Second operating level OL 2 0 No second operating level 1 Optimisation 2 Alarm functions and their hysteresis 4 Reserved no function yet 8 Second setpoint SP 2 16 Setpoint ramp SP r Result of...

Reviews: