A 43
3.3
Modbus register addresses
List of supported register addresses:
•
Type
A
: 16-bit values unsigned (one register = 2 bytes: 0 to 65535)
•
Type
C
: 32-bit values unsigned (two registers = 4 bytes: 0 to 4294967295)
For all 32-bit values / type C (energy counters, maximum demand (energy
feed)- und maximum values):
Address “Addr” := High-Word (2 bytes)
Address “Addr + 1” := Low-Word (2 bytes)
Modbus
Address
(Type)
SIGLON
Address
(+40001)
Description
Correspondent
SCTM-Address
Status Registers
9900 (C)
49901C
Modbus address (device ID)
9902
(C)
49903C
Version (integer, e.g. 10500 for 1.05.00)
700-01
9904
(A)
49905A
Version day and time: year,
e.g. for 29.06.2009: Addr. 9904=2009
700-02
9905 (A)
49906A
Version day and time: month*100+day
e.g. for 29.06: Addr. 9905=0629 (629)
700-02
9910 (C)
49911C
Time (seconds since 01.01.1990)
000-00
9912 (C)
49913C
Timestamp for last reset (seconds)
109-xx
9914 (C)
49915C
Timestamp for last Tm1 (seconds)
Newest (PP-01)
9916 (C)
49917C
Timestamp for last Tm2 (seconds)
Newest (PP-02)
9918 (A)
49919A
Registration period length Tm1 (minutes) 701-00
9919 (A)
49920A
Registration period length Tm2 (minutes) 701-00
9920 (A)
49921A
Device status of Tm1
2
700-2y, y=1
9921 (A)
49922A
Device status of Tm2
2
700-2y, y=2
9922 (A)
49923A
State of logic inputs
4
660-nn, nn=0..3
Meter Values
xx00 (C)
1
4xx01C
Pulse count for an input
130-xx
xx02 (C)
4xx03C
Counter value total actual
4rt-xx, r =0, t=5..9
xx04 (C)
4xx05C
Counter value T1 actual
xx06 (C)
4xx07C
Counter value T2 actual
xx08 (C)
4xx09C
Counter value T3 actual
xx10 (C)
4xx11C
Counter value T4 actual
xx12 (C)
4xx13C
Counter value total last reset
4rt-xx, r =1, t=5..9
xx14 (C)
4xx15C
Counter value T1 last reset
xx16 (C)
4xx17C
Counter value T2 last reset
xx18 (C)
4xx19C
Counter value T3 last reset
xx20 (C)
4xx21C
Counter value T4 last reset
xx22 (C)
4xx23C
Counter value total last Tm1
10t-xx, t=0..4
xx24 (C)
4xx25C
Counter value T1 last Tm1
xx26 (C)
4xx27C
Counter value T2 last Tm1
xx28 (C)
4xx29C
Counter value T3 last Tm1
xx30 (C)
4xx31C
Counter value T4 last Tm1
xx32 (C)
4xx33C
Counter value total last Tm2
11t-xx, t=0..4
xx34 (C)
4xx35C
Counter value T1 last Tm2
xx36 (C)
4xx37C
Counter value T2 last Tm2
xx38 (C)
4xx39C
Counter value T3 last Tm2
xx40 (C)
4xx41C
Counter value T4 last Tm2
xx42 (C)
4xx43C
Counter value current total actual
5rt-xx, r=0, t=5..9
xx44 (C)
4xx45C
Counter value current T1 actual
Summary of Contents for DLX
Page 9: ...9 1 Scope of Application 1 1 Application environment Figure 1 Application environment...
Page 42: ...42 4 2 Installation diagram Figure 13 Dimensions of mounting points...
Page 54: ...54 7 Menus 7 1 Flow diagram Figure 24 Flow diagram of menus...
Page 110: ...Subject to change without notice...
Page 111: ...E116012215052 Appendix A Data Retrieval Protocols...
Page 112: ...A 2...
Page 156: ...Subject to change without notice...
Page 157: ...E116012215052 Appendix B Table Addresses...
Page 158: ...B 2...
Page 170: ...Subject to change without notice...
Page 171: ...E116012215052 Appendix C List of Parameters and Constants...
Page 172: ...C 2...
Page 178: ...Subject to change without notice...