32
3.7.3
Rate control inputs
The rate control inputs TR1 to TR4 determine (if desired and if present in
the customer specific hardware configuration) the currently active energy
rate and maximum demand rate. The usage of inputs and the correlation of
input states to rates can be programmed freely (settable).
The factory default settings use TR1 to switch between two energy and
demand rates.
TR1
TR2
TR3
TR4
Energy rate mask
Demand rate mask
TR1
TR2
TR3
TR4
Energy
Demand
0
-
-
-
AT1
MT1
1
-
-
-
AT2
MT2
The state of deactivated control inputs (in our example: TR2, TR3 and
TR4) has no influence on the rate control (no matter whether the state
is 0 = open or 1 = closed).
If other combinations are desired, they can be programmed (see user man-
ual of DLXPARA).
Example: rate control for 4 energy rates and 2 demand rates, controlled by TR1, TR2
and TR3.
TR1
TR2
TR3
TR4
Energy rate mask
Demand rate mask
TR1
TR2
TR3
TR4
Energy
Demand
0
0
0
-
AT1
MT1
1
0
0
-
AT1
MT2
0
1
0
-
AT2
MT1
1
1
0
-
AT2
MT2
0
0
1
-
AT3
MT1
1
0
1
-
AT3
MT2
0
1
1
-
AT4
MT1
1
1
1
-
AT4
MT2
Summary of Contents for DLX
Page 9: ...9 1 Scope of Application 1 1 Application environment Figure 1 Application environment...
Page 42: ...42 4 2 Installation diagram Figure 13 Dimensions of mounting points...
Page 54: ...54 7 Menus 7 1 Flow diagram Figure 24 Flow diagram of menus...
Page 110: ...Subject to change without notice...
Page 111: ...E116012215052 Appendix A Data Retrieval Protocols...
Page 112: ...A 2...
Page 156: ...Subject to change without notice...
Page 157: ...E116012215052 Appendix B Table Addresses...
Page 158: ...B 2...
Page 170: ...Subject to change without notice...
Page 171: ...E116012215052 Appendix C List of Parameters and Constants...
Page 172: ...C 2...
Page 178: ...Subject to change without notice...