5.4.4
Connector X3 (Pulse inputs 1-6, outputs 1-4)
Terminal type:
Combicon MSTB2,5/10-ST-5,08 (Phoenix),
2 per input / output card
Function:
Inputs (In1 to In6, terminal 1 to 12)
Electronic outputs (Out1 to Out4, terminal 13 to
20)
Types of inputs / outputs: 6 input modules (IES, IEW, IED, signal current)
4 output modules (solid state IAW el., max.
250V/100mA)
Terminal Description
1
Pulse input
In1–
IN1
2
Pulse input
In1+
3
Pulse input
In2–
IN2
4
Pulse input
In2+
5
Pulse input
In3–
IN3
6
Pulse input
In3+
7
Pulse input
In4–
IN4
8
Pulse input
In4+
9
Pulse input
In5–
IN5
10
Pulse input
In5+
11
Pulse input
In6–
IN6
12
Pulse input
In6+
Freely programmable outputs
13
Electronic output
Out1–
OUT1
14
Electronic output
Out1+
15
Electronic output
Out2–
OUT2
16
Electronic output
Out2+
17
Electronic output
Out3–
OUT3
18
Electronic output
Out3+
19
Electronic output
Out4–
OUT4
20
Electronic output
Out4+
Figure 20, Connector X3
When IED (bi-current / bi-polar) Modules are used, then the signal
conditioning must be adjusted by means of the programming soft-
ware "DLXPARA".
When using mixed types of pulse inputs, the IES type modules are lo-
cated at the left hand side.
Summary of Contents for DLX
Page 9: ...9 1 Scope of Application 1 1 Application environment Figure 1 Application environment...
Page 42: ...42 4 2 Installation diagram Figure 13 Dimensions of mounting points...
Page 54: ...54 7 Menus 7 1 Flow diagram Figure 24 Flow diagram of menus...
Page 110: ...Subject to change without notice...
Page 111: ...E116012215052 Appendix A Data Retrieval Protocols...
Page 112: ...A 2...
Page 156: ...Subject to change without notice...
Page 157: ...E116012215052 Appendix B Table Addresses...
Page 158: ...B 2...
Page 170: ...Subject to change without notice...
Page 171: ...E116012215052 Appendix C List of Parameters and Constants...
Page 172: ...C 2...
Page 178: ...Subject to change without notice...