Examples for read out with
secondary address
:
Master:
68 0B 0B 68 53 FD 52 00 00 00 00 FF FF FF FF 9E 16
(selection with the
secondary address: 00 00 00 00)
Answer:
E5
Master:
68 0B 0B 68 53 FD 52 FF FF FF FF FF FF FF FF 9A 16
(selection with the
secondary address: wildcard FF FF FF FF
Hex
)
Answer:
E5
Master:
68 0B 0B 68 53 FD 52 87 98 16 04 FF FF FF FF D7 16
(selection with the
secondary address: 04 16 98 87
Hex
)
Answer:
E5
Master:
10 7B FD 78 16
(REQ_UD2: Request User Data)
Answer:
68 EA EA 68 08 7B 72 87 98 16 04 A8 15 00 02 02 00 00 00 04 03 77 15
00 00 C4 05 03 6D 13 00 00 84 10 03 E6 0F 00 00 C4 15 03 A8 0E 00 00
84 20 03 90 05 00 00 C4 25 03 C5 04 00 00 04 FB 82 73 F5 02 00 00 C4
05 FB 82 73 06 02 00 00 84 10 FB 82 73 E5 01 00 00 C4 15 FB 82 73 54
01 00 00 84 20 FB 82 73 0F 01 00 00 C4 25 FB 82 73 B1 00 00 00 04 2B
0C 00 00 00 04 AB FC 01 00 00 00 00 04 AB FC 02 00 00 00 00 04 AB FC
03 0C 00 00 00 04 FB 14 05 00 00 00 04 FB 94 FC 01 00 00 00 00 04 FB
94 FC 02 00 00 00 00 04 FB 94 FC 03 05 00 00 00 04 FD D8 FC 01 0C 00
00 00 04 FD D8 FC 02 08 00 00 00 04 FD D8 FC 03 08 03 00 00 04 FD C7
FC 01 3F 00 00 00 04 FD C7 FC 02 38 00 00 00 04 FD C7 FC 03 49 59 00
00 04 FB 2D 87 13 00 00 32 16
(RSP_UD: Respond User Data)
Master:
10 40 FD 3D 16
(deselection of the secondary address allocation)
Answer:
E5