INSTALLATION
MOUNTING THE STATION HOUSING
3 - 12
I-E96-117B
®
station. Refer to Table
for termination unit and SAC sta-
tion analog input designations. The KDS and KCS cables are
functionally equivalent except for the number of analog inputs
routed to the SAC station. The KDS cable only supports one
analog input (AI1) while the KCS cable supports two analog
inputs (AI1 and AI2). Refer to Tables
for
Figure 3-2. Station Housing Panel Cutout and Mounting Dimensions
NOTES:
1. MINIMUM CLEARANCE REQUIRED TO REMOVE STATION FROM HOUSING IS
250.0 MM (9.84 IN.).
2. MINIMUM CLEARANCE BEHIND PANEL IS 457.0 MM (18.00 IN.).
3. ALLOWABLE MOUNTING ANGLE OF FRONT PLATE IS 0 TO 75 FROM VERTICAL.
4. STANDARD ENVIRONMENTAL SPECIFICATIONS FOR THE SYSTEMS ARE
APPLICABLE .
66.0
2.60
138.0 ±1.0
5.43 ±0.04
144.0
5.67
25.4
1.00
2.54
0.10
TYP
MIN.
CLEARANCE
PANEL
CUTOUT
DIMENSION
+0.0, -1.0
+0.00, -0.04
72.0
2.83
A
(72.0 MM
NO. UNITS) – 5.8 MM
(2.83 IN.
NO. UNITS) – 0.23 IN.
×
×
A =
1.50 R MAX. TYP
0.06
T00297A
DIMENSIONS
MILLIMETERS
INCHES
381.0
15.00
229.1
9.02
BEND
RADIUS
136.0
5.35
2.3 - 25.4
0.09 - 1.00
PANEL
THICKNESS
76.2
3.00
97.5
3.84
127.0
5.00
152.4
6.00
NKDS03
NKTD02
NKTD12
NKDS13
NKCS01
NKCS02
NKCS11
NKCS12
CABLE
BEND
RADIUS
Table 3-10. Termination Device and SAC Station
Designator Relationship
Termination Device
Connector
Analog Input
Station
Designator
NTCS04 Termination
Unit
P2
AI3
AI1
P2
AI1
AI2
P3
AI4
AI1
P3
AI2
AI2
NICS01/NIDS01
Termination Module
AO1
AI3
AI1
AO2
AI4
AI1