INSTALLATION
MOUNTING THE STATION HOUSING
I-E96-117B
3 - 13
cabling applications, connections and length restrictions. Refer
to the appropriate termination unit manual for complete hard-
ware descriptions.
NOTES:
1.
The maximum cable length for the NKCS01, NKCS02 and
NKTD02 cables also depends on the number of stations intercon-
nected and the type of power system used. Tables
and
define the cable lengths depending on the power system and the
number of SAC stations used.
2.
Analog Inputs AI1 and AI2 are not available with the ICS termi-
nation module. AI1 may be displayed with the ICS/IDS pair. AI2 is
not available with the ICS/IDS pair.
Table 3-11. Cable Applications, Connections and Length Requirements
Cable
Connections
Maximum Length
From
To
Meters
Feet
Device
Connector
Device
Connector
NKCL01 and
NKCL11
NKTL01 cable
N-type plug
NKTL01
N-type plug 3,000.0
10,000.0
NKCS01 and
NKCS11
TCS termination unit
P2 or P3
SAC station
P1
137.16
450.00
TRL termination unit
P3
Refer to Tables
and
NKCS02 and
NKCS12
TCS termination unit
P2 or P3
First SAC
station of
interconnected
stations
P1
137.16
450.00
TRL termination unit
P3
Refer to Tables
and
NKDS01 and
NKDS11
TCS termination unit
P2 or P3
SAC station
P1
122.0
400.0
TRL termination unit
P3
Refer to Tables
and
NKDS02 and
NKDS12
TCS termination unit
P2 or P3
First SAC
station of
interconnected
stations
P1
122.0
400.0
TRL termination unit
P3
Refer to Tables
and
NKDS03 and
NKDS13
Interconnected SAC
station
NKDS02,
NKDS12,
NKCS02,
NKCS12,
NKDS01 or
NKDS13
connector
Interconnected
SAC station
P1
3.0
10.0
NKLM01 and
NKLM11
IMRIO02 module
P3
NTRL03
termination unit
P1
61.0
200.0
NKPL01 and
NKPL11
NTRL03 termination
unit
TB2, 5 and 6 NTRL03
termination unit
TB2, 1 and
2
2,000.0
6561.0