INSTALLATION
MOUNTING THE STATION HOUSING
3 - 14
I-E96-117B
®
NKSE01 and
NKSE02
TCS termination unit
P5
TCS
termination unit
P4
61.0
200.0
TCS termination unit
P4
TMP
termination unit
P4
NKTD01 and
NKTD11
IDS termination mod-
ule
P1
SAC station
KDS cable
connector
connected
to SAC sta-
tion
0.61
2.00
NKTD02 and
NKTD12
ICS termination mod-
ule
J2
SAC station
P1
183.0
600.0
Refer to Tables
and
NKTM01
MFP module
P3
IMP or ICS
termination unit
P1
30.0
100.0
NKTU01 and
NKTU11
CIS module
P3
TCS
termination unit
P1
61.0
200.0
Primary MFP module P3
TMP
termination unit
P2
Redundant MFP
module
P3
TMP
termination unit
P1
NKTU02 and
NKTU12
MFP or CIS module
P3
IMP or ICS
termination
module
P1
61.0
200.0
R2041-1976
twisted pair
ICS termination mod-
ule
TB21 and
TB22
IMP termination
module
P7
61.0
200.0
Table 3-11. Cable Applications, Connections and Length Requirements
(continued)
Cable
Connections
Maximum Length
From
To
Meters
Feet
Device
Connector
Device
Connector
Table 3-12. INFI 90 Power System Maximum Cable Length
Number of
Stations
Cable
Maximum Length
Meters
Feet
1
NKCS01, NKCS02, NKDS01,
NKDS02 or NKTD02
137
450
2
NKCS02, NKDS02 or NKTD02
60
200
3
NKCS02, NKDS02 or NKTD02
45
150
4
NKCS02, NKDS02 or NKTD02
30
100