INSTALLATION
MOUNTING THE STATION HOUSING
3 - 16
I-E96-117B
®
2. Connect the successive stations (maximum of 8, 4 from P2,
4 from P3) to the first station using a KCS (only 1 analog input
with KDS), NKDS02 or NKDS12 cable. There is an additional
connector on the KCS or KDS that connects to the NKDS03
and NKDS13 cable. Figure
shows a diagram of an intercon-
nected installation.
NOTE: Only the first interconnected SAC station can bypass an
analog output. The first interconnected SAC station connected to P2
of the TCS termination unit bypasses analog output number 1. The
first interconnected SAC station connected to P3 of the TCS termi-
nation unit bypasses analog output number 2.
Cable Connections for the NTRL03 Termination Unit
Figure
shows the cable connections for the NTRL03 termi-
nation unit. For more information refer to the
NTRL02 and
NTRL03 Fiber Optic Remote Link and Electrical Remote
Link Termination Units
product instruction.
Cable Connections for the NIRL03 Termination Module
Figure
shows the cable connections for the NIRL03 termi-
nation module. For more information refer to the
NIRL03
Remote Link Termination Module
product instruction.
Figure 3-3. Cable Connections for Two Analog Control Stations on One TCS Termination Unit
IMCIS02
IMMFP01/02/03
P1
P1
P3
P3
P2
P2
NKTU01/11
NKTU01/11
NKTU01/11
NKSE01/11
T00298A
NKSE01/11
NKSE01/11
NKDS01/11
NKCS01/11
NKDS01/11
NKCS01/11
TO
REDUNDANT
MFP
TO SECOND
GROUP OF UP
TO 32 STATIONS
TO ADDITIONAL NTCS04
AS REQUIRED
(32 STATIONS MAX)
P2
P2
P3
P1
P1
P7
P5
P5
P4
P6
P4
P3
NTMP01
NTCS04
IISAC01
(WITH BYPASS)
IISAC01
(WITH BYPASS)
P1
P1