INSTALLATION
3 - 12
I-E96-225A
®
INSTALLING THE MODULE
NOTE: Before installing the IMCPM03 module, check the MMU
backplane for -30 VDC. If the system uses an NAMM01, NAMM02,
NLMM01, NCOM01 or NCOM02 module, then -30 VDC is required.
Set J12 before installing the IMCPM03 module into the system.
1. Face the rear of the cabinet. Locate the -30 VDC Faston
™
connector. It is the second Faston from the top of the MMU
backplane.
2. Check for -30 VDC with respect to system common at the
-30 VDC Faston. The -30 VDC is not connected in INFI 90
Open systems.
3. If the system does not require -30 VDC, disconnect the -30
VDC supply wiring Faston or set jumper J12 before installing
the IMCPM03 module.
4. Set jumper J12 correctly. Refer to
5. For additional information or assistance, contact Elsag
Bailey technical support.
Figure 3-7. Controlway Cable Installation
T P 5 0 32 0 A
™ Faston is a trademark of Amp Incorporated.