TROUBLESHOOTING
ERROR MESSAGES
5 - 2
WBPEEUI110501A0
CELL TEMPERATURE
OVER LIMIT
PTS
Cell temperature input is
over/under factory specified
limits.
Remove the source of temperature extreme.
CELL TEMPERATURE
UNDER LIMIT
COMMAND ABORTED
STT03E
pressed before
function was completed.
Try function again.
CONFIG TAGNAME
ALREADY EXISTS
All
Attempted to copy a
configuration to a cartridge
or field device where it
already exists.
Erase old configuration before copying new
one. Refer to
DAMAGED
CELL OR
CHARACTERIZATION
BOARD
PTS
Characterization board or
cell is damaged.
Replace amplifier assembly. Refer to repair/
replacement section of the appropriate prod-
uct instruction.
Replace cell/characterization board. Refer to
repair/replacement section of the appropriate
product instruction.
DEVIATION
ALARM
AVS
Deviation has been greater
than the alarm setting for
two minutes.
Check valve.
Check PID tuning.
DYNAMIC
TEMPERATURE
MEASUREMENT
FAILURE
PTS
Dynamic temperature input
exceeded limits set at fac-
tory.
NOTE:
The temperature of the high
side of the cell with respect to the low
side of a PTS.
Output may no longer be accurate. Remove
source of temperature shift.
ELECTRONICS
TEMPERATURE
MEASUREMENT
FAILURE
EQS
PTS
Hardware failure of
on-board temperature sensor.
Replace amplifier assembly. Refer to repair/
replacement section of the appropriate prod-
uct instruction.
ELECTRONIC
TEMPERATURE
OUT OF RANGE
PTS
Electronics temperature is
outside the factory specified
limit.
Remove the source of the temperature
extreme.
ERROR! ATTEMPT TO
CONFIGURE
DUPLICATE
ADDRESS
All
Attempt was made to assign
an analog mode transmitter
an address on FBS module.
Be sure transmitter is in the correct mode
(analog or digital). Use
to verify mode.
Section 4 for details.
Attempt was made to assign
a digital mode transmitter to
an occupied FBS address.
Assign transmitter to an unoccupied address
or channel number of FBS module.
FIELD DEVICE CAN'T
EXECUTE
COMMAND:
COMMAND CONFLICT
BCN
EQN
TBN
Commands were sent by
STT03E terminal in the
wrong order. Verify
IMFBS01 is off-line if
STT03E terminal is in use.
Try command again.
Table 5-1. STT03E Error Messages
(continued)
Message
AffectedD
evice
Probable Cause
Corrective Action
CLEAR