EQN TEMPERATURE TRANSMITTER
CALIBRATION
C - 6
WBPEEUI110501A0
D-to-A Adjust
The
D-TO-A ADJUST
selection is only present when you are in the
ANA-
LOG
communication mode, specified in the configuration procedure. This
selection allows you to adjust the four to twenty milliamp output of the field
device.
Select
BENCH CALIB.
Apply 0 mV to the transmitter.
Apply 25 mV to the transmitter.
Enter the field device ambient temperature in degrees Cel-
sius using the number keypad. The surrounding room tem-
perature can be used for this temperature value.
Adjust the transmitter output using the up and down arrow
keys.
Adjust the transmitter output using the up and down arrow
keys.
Bench calibration is complete.
Key
Display
Comments
ENTER
CALIBRATION
D-TO-A ADJUST
→
BENCH CALIB.
ENTER
APPLY 0 mV
SIGNAL
THEN HIT ENTER
ENTER
APPLY 25 mV
SIGNAL
THEN HIT ENTER
ENTER
ENTER XMITTER
AMBIENT TEMP.
nn.nn C
ENTER
ADJUST TO 4 mA
THEN HIT ENTER
ENTER
ADJUST TO 20 mA
THEN HIT ENTER
ENTER
CONFIG. ID TAG
READY