Electrical Control Function
Electrical Control System
63
4-Way valve
Indoor fan
Outdoor fan
480P
PMV
PMV running
8 mins with 300P
Compressor
10S
30S
TimeA
10S
no longer than 10min
Condition of ending defrosting:
If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating
mode.
①
The defrosting time achieves 10min;
②
T3
≥
15
℃
;
③
T3
≥
7
℃
for 60seconds.
1.3.3.5 High evaporator coil temp.T2 protection:
T2>60
℃
, the compressor will stop and restart when T2<54
℃
.
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
For
12k models:
ΔT=T1-Ts
Running mode
ΔT
>
1
℃
Cooling
-1<ΔT≤1
℃
Fan-only
ΔT≤-1
℃
Heating