Copyright 2020 Baker Hughes Company. All rights reserved.
Page 116 of 277
Table 27: Motor Underload Menu Common Installations (cont'd.)
Parameter
Default
Description
Trip Delay
30.0 Seconds
Time to tolerate an underload
situation when the drive is
running. Set this time as long
as possible without causing heat
damage to the motor.
Restarts/Allowed
0
Set to non-zero to allow for
automatic restarts on a Motor
Underload fault.
Restart Delay
Global Restart
Delay between the fault and an
automatic restart.
ULoad@Min Freq
0 Amps
Defines an enhanced motor
protection mode in which the
underload limit is ramped up
from the ULoad@Min Freq to
the Motor Underload value at
Max Frequency. Setting this
parameter to 0 Amps (default
value) disables the enhanced
Underload protection mode (the
underload threshold the same at
all frequencies).
Navigate between pages of the menu by pressing the Left Arrow and Right Arrow buttons. The second
screen of menu is shown in
Figure 89: Underload Menu-Screen 2, page 117
. Changes on this page would
be very rare.
Summary of Contents for Apollo 3
Page 1: ...Copyright 2020 Baker Hughes Company All rights reserved Page 1 of 277...
Page 266: ...Copyright 2020 Baker Hughes Company All rights reserved Page 266 of 277 Figure 227 USB Menu...
Page 267: ......
Page 276: ......
Page 277: ...Index 129112 28 197705 28 197349 28 800638 28 197350 28 810280 28 197351 29...