10.3
Trigger Types (Basic)
“Basic” Trigger Types are appropriate for at least 90% of the triggers that will need to be field configured.
These types are automatically selected when the user executes the
“Add a Trigger” function from the
Channel Info screen. See Trigger Types (full list) below for all trigger types.
Table 58: Trigger Types (basic)
Action
(User Level)
Description
Is ON or SET
(Basic)
Activates when the Source 1 digital channel is ON.
This type of trigger is added when the user Adds a
Trigger to a digital channel from the Channel Info
screen.
Is LESS THAN
(Basic)
Activates when the Source 1 value is less than the
limit. This type of trigger can be selected when the
user Adds a Trigger to an analog channel from the
Channel Info screen.
Is GREATER THAN
(Basic)
Activates when the Source 1 value is greater than
the limit. This type of trigger can be selected when
the user Adds a Trigger to an analog channel from
the Channel Info screen.
10.4
Trigger States
Table 59: Trigger States
Trigger State
Color Scheme
(Text Color)
Description
Clr-Not In Use
Gray
The trigger is not in use in this
template (or has been disabled
by a user). This trigger will never
affect the motor control state
machine.
Clr-No Init.
Gray
The trigger has not been
initialized. This indicates that
it depends upon a channel or
another trigger that has not been
initialized. Navigate to the Trigger
Info screen to trace back to the
channel or trigger that is not yet
initialized.