Copyright 2020 Baker Hughes Company. All rights reserved.
Page 113 of 277
Figure 87: Overload Menu-Screen 2
Table 26: Motor Overload Menu Common Installations Screen 2
Parameter
Default
Description
OLoad@MinFreq
0.0 Amps
Defines an enhanced Overload
function. The overload threshold
is ramped up between this
value (at Min Frequency) to
the Motor Overload setting (at
Max Frequency). The enhanced
overload function is disabled
when the value is set to 0
(overload threshold is the same
at all frequencies).
OLoad Drain
3600 Seconds
When motor amps are below
the Overload threshold, the
bucket will be draining. This
value is the time for the
overload bucket to drain from
100% to 0% when motor amps
is 0. This time models the
motor cooling time. Higher
amps result in slower draining.
Summary of Contents for Apollo 3
Page 1: ...Copyright 2020 Baker Hughes Company All rights reserved Page 1 of 277...
Page 266: ...Copyright 2020 Baker Hughes Company All rights reserved Page 266 of 277 Figure 227 USB Menu...
Page 267: ......
Page 276: ......
Page 277: ...Index 129112 28 197705 28 197349 28 800638 28 197350 28 810280 28 197351 29...