Figure 101: Selecting a Trigger
Each channel has a warning trigger (trigger name has
“Hot” appended to the channel name) and a fault
trigger (trigger name has
“OH” (Over Heat) appended to the channel name). Warning triggers will keep
the drive from starting but will not stop the drive if it is already running (LOG->NO_START action). Fault
triggers will shut down a running drive (STOP->FAULT action). Select the trigger you wish to set up. By
default, the triggers are Not In Use.
Figure 102: Trigger Info Screen Indicating the Trigger is “Not In
Use”