Masoneilan 4700P/E & 4800P/E Positioners Manual | 51
© 2021 Baker Hughes Company. All rights reserved.
Troubleshooting
The following conditions must exist to ensure satisfactory operation of the positioner:
•
The valve must be properly mounted in the line so that the actuator counters the
dynamic torque and the valve operates as desired on air failure.
•
Supply pressure is adequate for valve operation. See pressure drop tables in valve
catalog.
•
Correct positioner installation.
•
Correct positioning of the feedback (cam, bearing lever, etc.).
•
Proper cam selection.
•
Supply, instrument signal and output connections must be correct for the positioner
action (i.e., direct or reverse).
•
Air tight connections.
•
Correct position of the bypass.
In case of malfunction, check following in order given:
1. Check zero adjustment and adjust the zero nut (4B) if necessary. Lock with locknut (4C).
2.
Check span adjustment and adjust if necessary.
3. Adjust instrument signal pressure from minimum to maximum and observe the
corresponding gauge. If Instrument gauge reading does not respond to the signal, the
diaphragm S/A may be broken. Replace the defective part.
4.
Positioner insensitivity may be the result of a sticking pilot spool whose movement may be
impeded by:
a. Foreign matter such as dirt, metal particles, etc.
b. Partial blockage of air passages caused by too much oil in the air lines.
c. Blocking of vent holes.
Summary of Contents for Masoneilan 4700P
Page 16: ...2021 Baker Hughes Company All rights reserved 16 Baker Hughes Figure 5 87 88 Actuator...
Page 30: ...2021 Baker Hughes Company All rights reserved 30 Baker Hughes Figure 12 FM Installation...
Page 32: ...2021 Baker Hughes Company All rights reserved 32 Baker Hughes Figure 14 ATEX Installation...
Page 64: ...2021 Baker Hughes Company All rights reserved 64 Baker Hughes NOTES...