Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
| 63
© 2020 Baker Hughes Company. All rights reserved
.
CAUTION
Use of a low impedance voltage source will damage
the SVI II AP. The current source must be a true high
impedance current limiting device. A proper current
source explicitly enables adjustment of the current in
mA, not V.
To power up the SVI II AP:
1. Loosen the four (4) cover screws and remove the cover of
the SVI II AP. Connect the +
⁄
- terminals to the current
Reinstall the cover and display.
2. Adjust current to 12 mA. On initial power up of a newly
installed SVI II AP, the positioner runs in NORMAL mode
using the default instrument parameters installed at the
factory. The positioner cycles through the NORMAL cycle
menu and LCD displays the following values:
PRES: Pressure - unit of measurement and value*
SIGNAL
POS (Position)
An exclamation point (
!
) appears in the top left corner of
the display window to indicate that there is further
instrument status available.
3. Proceed to Configuration and Calibration.
* For firmware version 3.2.1, the supply pressure appears on
the LCD. Additionally, Stops results and Autotune results, stay
displayed until cleared.
NOTE
If the SVI II AP is specified without local pushbuttons
and display, local operation is not available. Configure
and calibrate with ValVue and a HART
®
modem.