Table 14
High Flow Pneumatics Single Acting High Flow
Air Supply
Dry, oil-free, 5 micron filtered air (See ISA S7.3)
Action
Direct Acting
Supply Pressure
20 -100 psi max. (1.4 - 6.9 bar)
Regulate 5 - 10 psi (.345 bar - .69 bar) above actuator
spring range. Do not exceed actuator rating.
Air Delivery - Single Acting Relay
39.0 scf/min. (1104 L/min) at 30 psi (2.1 bar) sup-
ply
70.6 scf/min. (2000 L/min) at 60 psi (4.2 bar) sup-
ply
102.0 scf/min. (2888 L/min) at 90 psi (6.3 bar) sup-
ply
Air Capacity
(flow coefficient)
Loading CV = 2.2
Venting CV = 2.8
Air Consumption
0.28 scf/min. (8.0 L/min) at 30 psi (2.1 bar) supply
0.35 scf/min. (10.5 L/min) at 45 psi (3.1bar) supply
Air Supply Failure
Single Acting Relay
On supply failure the actuator output drops. Some over-
shoot may occur when air pressure returns after a
period without air supply pressure. Always set control
set point to 0%, and put the process control system in
manual, for smooth recovery from air supply failure.
Loss of Input Signal
Output drops to low pressure.
Output Pressure
0-150 psi (10 bar) max
Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
| 87
© 2020 Baker Hughes Company. All rights reserved
.