© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
28 |
=
BHGE
5. Slide the magnet holder into the extension shaft. The location of the magnets is in
the ring of the magnet holder. The magnetic axis is the imaginary line through the
center of both magnets.
6. Rotate the magnet holder so that the magnet axis is vertical when the valve is in
the closed position.
7. Align the end of the magnet holder flush with the end of the mounting bracket.
Secure the magnet holder with two M6 set screws.
8. Slide the V-Seal over the magnet holder.
9. Secure the SVI II AP onto the mounting bracket using four M6 x 20 mm socket
head cap screws.
10. Ensure no interference exists with the position sensor protrusion.
11. Ensure that the V-Seal makes contact with the skirt around the position sensor
protrusion on SVI II AP housing.
Summary of Contents for Masoneilan SVI II AP
Page 6: ...This page intentionally left blank...
Page 10: ...This page intentionally left blank...
Page 68: ...This page intentionally left blank...
Page 90: ...2018 Baker Hughes a GE company LLC All rights reserved 90 BHGE Spare Parts...
Page 92: ...2018 Baker Hughes a GE company LLC All rights reserved 92 BHGE...
Page 94: ...This page intentionally left blank...
Page 102: ...This page intentionally left blank...
Page 105: ...This page intentionally left blank...
Page 106: ...This page intentionally left blank...
Page 107: ...This page intentionally left blank...