Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
49
Figure 25
Magnet Orientation for Camflex and Varimax with Valve Closed
Figure 26
Magnet Orientation for 90° Valve Rotation with Valve Closed
Using ValVue to Check Magnet Position
Use this procedure to check the magnet using ValVue.
1. Connect to the positioner in accordance with the ValVue instructions.
a. Ensure the positioner has been installed and set up with a HART
®
Modem in a
HART
®
compliant communications loop, if required, install ValVue on the
computer that is connected to the HART
®
modem.
b. Run ValVue.
c. Select the installed positioner from the list of connected devices.
d. Select the
Raw Data
tab to view the current operating conditions of the selected
positioner.
2. Read Raw Position data. When the valve is:
Closed, the value should be between – 1000 and +1000 for a reciprocating
valve or a 60° rotation rotary valve.
At mid-travel, the value should be between –1000 and +1000 for a greater
than 60° rotation rotary valve.
Magnet
Axis
with
Valve
Closed
Magnet
Axis
with
Valve Closed
Clockwise to Close
Clockwise to Open
45
¬
Summary of Contents for Masoneilan SVI II AP
Page 6: ...This page intentionally left blank...
Page 10: ...This page intentionally left blank...
Page 68: ...This page intentionally left blank...
Page 90: ...2018 Baker Hughes a GE company LLC All rights reserved 90 BHGE Spare Parts...
Page 92: ...2018 Baker Hughes a GE company LLC All rights reserved 92 BHGE...
Page 94: ...This page intentionally left blank...
Page 102: ...This page intentionally left blank...
Page 105: ...This page intentionally left blank...
Page 106: ...This page intentionally left blank...
Page 107: ...This page intentionally left blank...