Proceed with the following steps:
1. Press
NEXT.
2. Field device has more status available
3. Press
NEXT
4.
Ignore next 50 occurrences
of status?
5. Press
YES
6. Change to
MANual
mode
7. Scroll to line
6 EXAMINE
, press
->
8. Scroll down to
5 read status
.
9. Read message.
10. Press
OK.
11. Repeat
OK
to read all messages until the display returns to
read status
.
12. Scroll down to
6 clear status,
press
->
13. If
clear fault codes not completed
appears, press
OK
and read the message
(
Position Error,
for example) or go to the troubleshooting guide.
14. Correct the problem (Is the air supply on?), and then go to clear status until
Clear
Fault codes Completed
appears.
15. Press
OK
.