Table 15: Pneumatics Double Acting Standard Flow
Air Supply
Dry, oil-free, 5 micron filtered air see ISA S7.3
Action
Output 1 increases with increasing signal
Output 2 decreases with increasing signal
Supply Pressure for
Double Acting
25 - 150 psi max. (1.73 to 10.3 bar)
Do not exceed actuator rating.
Air Delivery for
Double Acting
7.2 scf/min. (204 L/min) at 30 psi (2.1 bar) supply
12.8 scf/min. (362 L/min) at 60 psi (4.2 bar) supply
18.3 scf/min. (518 L/min) at 90 psi (6.3 bar) supply
23.8 scf/min. (674 L/min) at 120 psi (8.3 bar) supply
Air Capacity
(flow coefficient)
Loading CV = 0.39
Venting CV = 0.33
Air Consumption for
Double Acting
0.4 scf/min. (11.3 L/min) at 30 psi (2.1 bar) supply
0.85 scf/min. (24.1 L/min) at 80 psi (5.52 bar) supply
Air Supply Failure
Positioner cannot control the failure position of an actuator without a spring. The actuator
can, under different conditions, fail in place, fail open, or fail close. In cases where the
valve must fail to a required position additional accessories are required.
Some overshoot can occur when air pressure returns after a period without air supply
pressure. Always set control set point to 0%, and put the process control system in man-
ual, for smooth recovery from air supply failure.
Loss of Input Signal
Output 1 fails to atmosphere
Output 2 fails to supply pressure.
Summary of Contents for Masoneilan SVI II AP
Page 6: ...This page intentionally left blank...
Page 10: ...This page intentionally left blank...
Page 68: ...This page intentionally left blank...
Page 90: ...2018 Baker Hughes a GE company LLC All rights reserved 90 BHGE Spare Parts...
Page 92: ...2018 Baker Hughes a GE company LLC All rights reserved 92 BHGE...
Page 94: ...This page intentionally left blank...
Page 102: ...This page intentionally left blank...
Page 105: ...This page intentionally left blank...
Page 106: ...This page intentionally left blank...
Page 107: ...This page intentionally left blank...