Inductive Load, Solenoid, Incandescent Lamp Configuration
Figure 35
Simplified Switch Installation Drawing: Correct Configuration
SVI II AP Switch Output:
1 V
with switch ON
External
Voltage
Source
LOAD
Load is designed to limit current through the switch to < 1 A.
+
-
If the load is inductive (solenoid,
incandescent lamp, etc.), then install a
Freewheel or Flyback diode to prevent
switch damaging EMF voltage spikes.
+
-