Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
99
© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
The Burst mode is when the HART
®
device continuously sends out data for a device not capable
of being polled by a Master. Use this mode only for devices that are passive (i.e. not a HART
®
master), such as a HART
®
to Analog converter (SPA from Moore Industries, Tri-Loop by Rose-
mount). Turning on Burst mode in cases where it is not required affects the communication
bandwidth. Burst mode is not available for SVI II AP in HART
®
7.
To see how the Burst mode is configured see the ValVue or SVI II AP DTM online help.
The Burst mode can send the following commands:
Cmd1
: PV
Cmd2
: %range/current
Cmd3
: Dyn vars/current
Cmd9
: Device vars w/status
Cmd33
: Device variables
Choose the Burst command variables to be returned by referring to list of device variables in
Table
16.
Figure 37
Burst Mode Configuration
C. Burst Mode Operations