3.7.2 Before Powering Up
Before powering up the SVI3, Please ensure that all electrical and pneumatic connections
are as per ES-817 SVI3 Safety Manual.
3.7.3 Powering Up the SVI3
To power up the SVI3:
1. Connect the Control Loop wiring. Refer “Connecting to the Control Loop” on page 37.
2. Adjust current to 12 mA. On initial power up of a newly installed SVI3, the positioner
starts up in NORMAL mode and is operational in the default factory configuration. The
following values appear:
• POS (Position in percentage)
• PRES: (Pressure - unit of measurement and value)
• SIGNAL - Current input in mA
An exclamation point (!) in the top left corner of the display window indicates that
there is further instrument status available.
3. Proceed to calibration and configuration.
NOTE : For Hazardous Location Installation information refer to “Specifications and
NOTE : If the SVI3 is specified without local pushbuttons and display, local operation
is not available. Configure and calibrate with SVI3 DTM with Valvue or SVI3
DD files with HART Communicator.