Masoneilan SVI3 Installation and Maintenance Manual
=
| 59
© 2021 Baker Hughes Company. All rights reserved.
4.3.8.1 Clear Error Messages
Use this procedure, VIEW ERR, to view fault codes and messages listed in Table 10 on
page 76 of this manual. This is useful when clearing a Failsafe from the pushbuttons.
1. Press + in
NORMAL
or
MANUAL
mode to move through the options until you reach
the
VIEW ERR
menu item.
2. Press * to go to
VIEW ERR
menu.
3. Press * to display the list of status values.
4. Press + to move forward trough the list in sequence
.
5. Press – to move back through the list.
6. Press * at any status message to return to the
VIEW ERR
option in your previous
mode.
7. Press + to move to
Clear ERR
.
8. Press * to clear all messages (recommended) or press + to move to the next option.
4.3.8.2 Positioner Fault Messages
Table 10 on page 76 lists the fault codes and messages that appear on the display
.
The
table also explains the meaning of each message and a possible cause of the fault.
4.3.8.3 Return to Normal Operation
Always return the positioner to NORMAL operating mode to resume control by the input
signal. Use this procedure to return to NORMAL mode from any menu.
1. Press + or - repeatedly until
MANUAL
or
NORMAL
appears.
2. Press * to return to NORMAL operating mode, if
NORMAL
appears.
3. Press * to return to MANUAL Mode menu, if
MANUAL
appears.
4. Press + repeatedly until -›
NORMAL
appears.
5. Press * to return to
NORMAL
mode and normal operation
.
4.3.9 Configure Menu
Because calibration depends on certain configuration options you must perform
Configuration before you perform Calibration when installing the SVI3 for the first time.
If a change is made in the Air
-
to-Open / Air-to-Close configuration option or if you move
the SVI3 to a different valve or make any change to the valve position linkage
,
you must
run the find STOPS calibration again.
NOTE : When entered from NORMAL mode the valve still responds to changes in set
point input signal and the values displayed change in accordance with
changes in the input signal. When entered from MANUAL mode the valve is in
locked position.