4.3.9.5 Turning TS OFF
1. Press * to turn TS OFF
.
2. Press + to continue scrolling through the menu.
4.3.9.6 Changing Language
The local display language can be English or French.
1. Press * to toggle from ENGLISH to FRANCAIS.
2. Press + to continue to scroll through Config menu.
4.3.10 Calibration Menu
The Calibration menu shown in Figure 34 provides access to all the calibration functions
for the SVI3. If a change is made in the Air-To-Open/Air-To-Close configuration option or if
you move the SVI3 to a different valve or make any change to the valve mounting kit
components
,
you must run the find STOPS calibration again.
Figure 34 Calibration Menu
SETUP
+
+
+
Calibration Menu
STOPS
*
*
RUNNING
STOP OP
*
*
TUNE
*
*
*
TUNE ERR
STEP 1/3
STEP 2/3
+/-
*
CALIB
<VALUE>
* - +
<VALUE>
+/-
*
SIG LOW
*
<VALUE>
* - +
<VALUE>
+/-
*
*
STEP 3/3
If there is a calibration tuning error
TUNE ERR appears. Press * briefly and
automatically return to the start of TUNE.
STOPS FAIL
If there is a calibration stops error
STOPS FAIL appears. Press * briefly and
automatically return to the start of STOPS.
SIG HIGH
*
<VALUE>
* - +
<VALUE>
+/-
*
+
+
+
*
CALIB
CAUTION: These functions stroke the valve over its full range of travel.
Do not perform while the valve is controlling the process.
See Figure 27 for full
menu structure
Press the Hold
button at anytime
to cancel the
selected action
and return to the
menu item above
it in the navigation
tree.