Masoneilan SVI3 Installation and Maintenance Manual
=
| 93
© 2021 Baker Hughes Company. All rights reserved.
Air Supply Failure
Single Acting Relay
On supply failure the actuator output drops. Some overshoot
may occur when air pressure returns after a period without air
supply pressure. Always set control set point to 0%, and put
the process control system in manual, for smooth recovery
from air supply failure.
Loss of Input Signal
Output drops to low pressure.
Output Pressure
0-120 psi (8.27 bar) max
Table 15: Pneumatics Single Acting Standard Flow
Table 16: System Connectivity
HART
®
Physical Device Type
Actuator Device Type:
HART
®
7: 65AA (170)
DD Registered with FieldComm
TM
Group
Yes, available through FieldComm
TM
Group
Integration with HART
®
host software
Integrates with leading DCSs with full DTM and EDD sup
-
port, including, but not limited to:
• Baker Hughes / Valvue3
• Emerson DeltaV / AMS
• Honeywell / FDM
• Yokogawa / PRM
• GE MarkVle ControlST
Diagnostics
Travel odometer, Cycles, Time Closed/Open, Time Near
Closed, Alarms, Friction, Stick Slip, Spring Range, Error
Offset, RMS Error, Obstruction Detection, Calibration Error,
and Setpoint cycling tests
Ramp Test: Hysteresis, Deadband, Accuracy, Linearity
Step Test: Overshoot, Response resolution, Deadtime
Valve Signature: Spring Range, Friction, Seat Profile
Table 17: HART
®
Device Information
Item
Definition
Model Name
SVI3
Device Type Code
170 or 0x65AA (firmware 1.x)
Device Revision
1 if firmware 1.x