Template 56377 10-05-12
59340-91_59342-01_59310_59371_97_C 10-17-19
4
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
2-out-of-3-Service wiring options with Pump 2:
Pump 2 can either be wired to the Heater service or to the Pump 1 service.
If Pump 2 is wired to the Heater service, DIP Switch A8 ON (with other DIP swtiches OFF) makes Pump 2 shut OFF the heater, but lets Pump 1 run along with the Heater.
If Pump 2 is wired to the Pump 1 service, then the heater can always run (with DIP switches A2 and A3 both ON). However, in most cases DIP Swtich A5 also has to be ON,
which only allows either Pump 1 or Pump 2 (not both) to be at high speed at the same time The only case where DIP Switch A5 can be turned OFF is if both pumps are small
enough to fit in a single 16A service together with both pumps at high speed, together with any other equipment such as A/V.
When DIP switch A5 is ON, having one pump at high speed prevents you from turning the other pump to high speed. You have to turn the first pump to either low speed or OFF
before you can turn the other pump to high speed.
2-out-of-3-Service wiring options with Blower:
The Blower can either be wired to the Heater service or to the Pump 1 service.
If the Blower is wired to the Heater service, DIP Switch A8 ON (with other DIP swtiches OFF) makes the Blower shut OFF the heater, but lets Pump 1 run along with the Heater.
If the Blower is wired to the Pump 1 service, then the heater can always run (with DIP switches A2 and A3 both ON). However, in most cases DIP Swtich A5 also has to be ON,
which only allows either Pump 1 High or the Blower (not both) to run at a given time To determine whether DIP switch A5 can be turned OFF, add up the amperages of PUmp 1
High, the Blower, the Circ Pump (if any), the Ozone, and A/V (if any). If the sum of all this equipment is below 16A, DIP switch A5 can be trurned OFF.
When DIP swtich A5 is ON, the Blower is automatically turned OFF when Pump 1 goes to high speed. (If Pump 1 then goes to low speed or turns OFF, the Blower may turn back
ON automatically.)
2-out-of-3-Service wiring options without ether Pump 2 or Blower:
When not using either Pump 2 or Blower, ie in Setups 5 - 7, the heater can run at any time with either of the above DIP swtich settings.
Basic Functions Setup 1 - 7