background image

IMPORTANT SAFETY INSTRUCTIONS

DANGER

  To reduce the risk of injury, do not permit children to use this product 

unless they are closely supervised at all times.

WARNING -

 RISK OF CHILD DROWNING. Extreme caution must be exercised to 

prevent unauthorized access by children. To avoid accidents, ensure that children 
cannot use a spa or hot tub unless they are supervised at all times.

DANGER

  To reduce the risk of injury to persons, do not remove suction fittings.

Spa location must accommodate sufficient drainage of water around the base of the 

structure, as well as the power source compartment.

Prolonged immersion in water that is warmer than normal body temperature can result 

in a dangerous condition known as HYPERTHERMIA. The causes, symptoms, 
and effects of hyperthermia may be described as follows: Hyperthermia occurs 
when the internal temperature of the body reaches a level several degrees above 
the normal body temperature of 98.6

B

F. The symptoms of hyperthermia include 

dizziness, fainting, drowsiness, lethargy, and an increase in the internal 
temperature of the body. The effects of hyperthermia include (1) unawareness of 
impending hazard, (2) failure to perceive heat, (3) failure to recognize the need to 
exit spa, (4) physical inability to exit spa, (5) fetal damage in pregnant women, (6) 
unconsciousness resulting in danger of drowning. WARNING  The use of alcohol, 
drugs or medication can greatly increase the risk of fatal hyperthermia in hot tubs 
and spas.

DANGER - 

RISK OF ELECTRICAL SHOCK. 

 A spa may be installed within 5 feet of metal surfaces if each metal surface is 

permanently connected by a solid copper conductor attached to the wire connector 

on the terminal box . Refer to NEC and local codes 

A bonding lug is provided on the control box to permit connection of a 

solid copper bonding conductor between this point and any equipment, metal 
enclosures of electrical equipment, metal water pipe, or conduit within 5 feet 
(1.5m) of the unit as needed to comply with local requirements.

Bond accessible metal to the dedicated connector on the equipment grounding bus, 

bond the equipment ground bus to the local common bonding grid as part of the 
installation in the form of (1) a reinforced concrete slab for support, (2) a ground 
plate provided beneath the hot tub or spa, or (3) a permanent ground connection 
that is acceptable to the local inspection authority. 

DANGER

  RISK OF ELECTRICAL SHOCK. Do not permit any electrical appliance, 

such as a light, telephone, radio, or television, within 5 feet (1.5m) of a spa or hot 
tub.

To reduce the risk of injury:

The water in a spa or hot tub should never exceed 104

B

F (40

B

C). Water temperatures 

between 100

B

F (38

B

C) and 104

B

F (40

B

C) are considered safe for a healthy adult. 

Lower water temperatures are recommended for extended use (exceeding 10-15 
minutes) and for young children.

Excessive water temperatures have a high potential for causing fetal damage during 

the early months of pregnancy, pregnant or possibly pregnant women should limit 
spa or hot tub water temperatures to 100

B

F(38

B

C).

!

!

!

!

!

Before entering the spa or hot tub, the user should measure the water temperature 

with an accurate thermometer.

The use of alcohol, drugs, or medication before or during spa or hot tub use may lead 

to unconsciousness with the possibility of drowning.

Persons suffering from obesity or with a medical history of heart disease, low or high 

blood pressure, circulatory system problems, or diabetes should consult a 

physician before using a spa or hot tub.

3

in effect at the time of 

installation.)

SpaDepot.com

Summary of Contents for 7100B-4.0-F

Page 1: ...CS7100B F SERIES LITE LEADER Series BALBOA Operation Manual Covers the following CS series 7100B F 7109B F 7100B 4 0 F 7109B 4 0 F SpaDepot com...

Page 2: ...l being replaced you may still need to modify the plumbing to achieve proper alignment VH Series Versi Heat Heater configuration This series is designed to allow the heater to be positioned within 60...

Page 3: ...l Cords 10 Power Connection 11 Cord Connections 12 System Plug Pinouts 12 Spa Light 12 Equipment Connections 13 Circuit Board Configurations 14 System Start Up 15 Filtration Cycles 15 Spa Side Control...

Page 4: ...minal box Refer to NEC and local codes A bonding lug is provided on the control box to permit connection of a solid copper bonding conductor between this point and any equipment metal enclosures of el...

Page 5: ...hat requires proper ventilation and is intended for outdoor use only For Permanently Installed Units For Permanently Installed Units not Provided with an Internal Disconnecting Method For Units with G...

Page 6: ...ion may be installed at the electrical service panel or a separate sub panel Use copper conductors ONLY The ground must be sized following the National Electric Code Table 250 122 For Power conductor...

Page 7: ...e to add it to an open slot in the panel Option 2 shows the power from main service panel to a GFCI subpanel within line of site of the spa Note Most local codes will allow a GFCI subpanel to be a dis...

Page 8: ...ROUND BUS BAR LINE LUG 1 LINE LUG 2 INCOMING SERVICE CONDUCTORS FROM MAIN PANEL NEUTRAL GROUND TO SPA CONTROL SYSTEM LOAD LOAD NEUTRAL MUST BE CONNECTED DIRECTLY TO GFCI AS SHOWN GFCI Wiring Detail Th...

Page 9: ...Step 5 Step 6 Step 7 Step 1 Step 2 Step 3 Remove the control system from the carton and verify contents for completeness If the application is a bottom mount install then you are ready to go directly...

Page 10: ...ealing surfaces and insert the drywell into the hole Tighten the drywell nut DO NOT over tighten Insert temperature sensor into drywell and insert grommet as shown below Allow silicone to cure for 24...

Page 11: ...plug for the control system saving you hours of install time 10 30 1220 L6 30 1180 L6 The Hydro Quip Lite Leader sensor kit has been developed to offer the maximum in flexibility Unlike the tradition...

Page 12: ...Blue White Neutral Wires Crimped Together Connect input Neutral to White Wire crimped together with Blue wire Connect Line 1 to Black Wire Connect Ground to Ground Lug provided inside control box Con...

Page 13: ...Speed Red Low Speed Black Common White Ground Green Note flat sides in connector Spa Light Your control may contain a high intensity low voltage light to enhance night time use This illustration shows...

Page 14: ...high speed Pump 1 is factory configured for 120V To convert pump 1 to 240V move the red coded white wire Common from N to L2 The ozone utilizes the black wire for L1 voltage and the white wire for ne...

Page 15: ...efault Connector J1 Spaside plug Connector J20 High Limit and Temperature sensor plug While looking at the board in the above orientation the high limit plugs in to the left side of the connector and...

Page 16: ...breaker at the electrical service panel 240 volt system 9 Adjust temperature to the lowest setting 10 Press the Lights Jets switch to run the pump on high speed Allow the pump to run until you achieve...

Page 17: ...spa and the equipment system Freeze related damage is not covered by the warranty Winterizing Chemical Water Treatment Your dealer is familiar with local water conditions and which chemicals are compa...

Page 18: ...ashing and begin to display the current spa temperature Temperature range 80 F 104 F 26 0 C 40 0 C The last measured temperature is constantly displayed on the LCD Spaside Control Operation 16 Press t...

Page 19: ...either the high limit or water temperature sensor malfunctions the display will show SN meaning sensor Contact your dealer or service organization Possible defective sensor Open Sensor Spa is deactiva...

Page 20: ...breaker at service panel Low Water Flow Clean or Replace filter No Heat High Heat Filter Cycles Running Too Long Adjust filter cycles down Temperature Set Too High Adjust Set Point High Ambient Tempe...

Page 21: ...stem turned OFF remove the wires from the pressure switch terminals secure wires safely to prevent any chance of electrical shock 2 Use temperature adjustment key to move set point temperature to its...

Page 22: ...witch is not closed rotate the pressure switch adjustment screw counter clockwise until the Ohmmeter indicates a CLOSED circuit 6 Re connect the heater control cord 7 Now test for proper operation of...

Page 23: ...use or care To obtain warranty service return defective products within the warranty period to Hydro Quip The Hydro Quip Limited Warranty is for service on the control box only Purchaser is responsib...

Page 24: ...85 0069C 1 Rev 01 10 18 SpaDepot com...

Reviews: