Confi guration Options
Reminder Features
Feature Default
Options
Increment
Reminders Shown*
Yes
Yes,
No
N/A
Check pH
OFF
See Reminder Period Note
1
Days
Check Sanitizer
OFF
See Reminder Period Note
1
Days
Clean Filter
30 Days
See Reminder Period Note
1
Days
Test GFCI
65 Days
See Reminder Period Note
1
Days
Drain Water
100 Days
See Reminder Period Note
1
Days
Change Cartridge
OFF
See Reminder Period Note
1
Days
Clean Cover
OFF
See Reminder Period Note
1
Days
Treat Wood
OFF
See Reminder Period Note
1
Days
Change Filter
365 Days
See Reminder Period Note
1
Days
Reminder Periods can be set between 7 and 180 days. In addition, 365 days can be chosen.
Each reminder can be turned OFF individually.
Special Features
Feature Default
Options
Increment
Special Amperage Rule A (DIP SW 5 OFF)
No Limitation
1 Pump
Special Amperage Rule B (DIP SW 5 ON)
1 High-Speed Pump**
1 Pump
1 to 7 pumps can run on high speed together.
Blower can be allowed or suppressed when number of pumps selected is reached.
“No Limitation” does not restrict pump or blower operation.
DIP Switch 5 is used to choose Special Amperage Rule 1 or 2.
Drain Mode
Disabled
Disabled, Enabled
N/A
Demo Mode
Disabled
Disabled, Enabled
N/A
Automatic GFCI Test
Disabled
Disabled, 1-7 Days
1 Day
When GFCI Test is Enabled, the Auto-Test can be set between 1 and 7 days from startup
Ozone Slaved to Heater Pump
Yes
Yes, No
N/A
Blue Indicates New Custom Confi guration Default (Setup 1)
* Editable by end-user
** Special Amperage Rule B is (DIP Switch 5 ON) is only used with Setup 1-16 (Page 4).
This setting will not allow both Pump 1 High and Pump 2 to run at the same time.
Options Increment
Yes, No
N/A
See Reminder Period Note
1 Days
See Reminder Period Note
1 Days
See Reminder Period Note
1 Days
See Reminder Period Note
1 Days
See Reminder Period Note
1 Days
See Reminder Period Note
1 Days
See Reminder Period Note
1 Days
See Reminder Period Note
1 Days
See Reminder Period Note
1 Days
Disabled, Enabled
N/A
Disabled, Enabled
N/A
Disabled, 1-7 Days
1 Day
days from startup
es, No
N/A
Options Increment
1
Pump
1
Pump
1 to 7 pumps can run on high speed together.
Blower can be allowed or suppressed when number of pumps selected is reached.
“No Limitation” does not restrict pump or blower operation.
DIP Switch 5 is used to choose Special Amperage Rule 1 or 2.
When GFCI Test is Enabled, the Auto-Test can be set between 1 and 7
Reminder Periods can be set between 7 and 180 days. In addition, 365 days can be chosen.
Each reminder can be turned OFF individually.